HEATING: GAS BURNER
BALTIC R410A-IOM-0708-E
Page 83
DISASSEMBLING THE GAS BURNER FOR
MAINTENANCE PURPOSES
Preliminary Safety Recommendations
Isolate the unit using the main isolator switch.
Close off the isolating gas valve located before the unit.
Disconnect the Pipe-work. Do not discard the seals.
Disassembling the gas
«
burner support bar
»
Disconnect the Electrical Connector on the electric
connection board EF47
Remove the two screws which hold the gas Bar in Place
Carefully remove the gas « burner support bar » avoiding
any damages to the electrodes.
Disassembling the flue
Electrically disconnect the fan and remove the screws
holding it in place.
Take care not to loose any cage nuts in the smoke box.
ATTENTION: Check the correct position of the pressure tube
used by the extraction pressure switch.
Required Equipment List for maintenance Adjustment
and Start-up
An accurate manometer from 0 to 3500 Pa (0 to 350 mbar):
0.1% full scale.
A Multimeter with Ohmmeter and Micro-amps scale
An Adjustable Spanner
Tube Spanner Set: 8, 9, 10, and 13.
Flat Screwdrivers diameter 3 and 4, Fillips n°1
Vacuum cleaner
Paint brush
GAS BURNER SUPPORT BAR
Fig. 61
Fig. 62
Fig. 63
Fig. 65
Fig. 66
Fig. 64
Summary of Contents for BAC020SNM
Page 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Page 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Page 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Page 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Page 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Page 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Page 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Page 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Page 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Page 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Page 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Page 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Page 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Page 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Page 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Page 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Page 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...