VENTILATION: AIRFLOW BALANCING
BALTIC R410A-IOM-0708-E
Page 61
2
nd
method when adjusting the pulley :
-Close the pulley fully and count the number of turns
from fully closed position. Using
table_2
determine the
motor pulley actual diameter.
-Record the fix fan pulley diameter.(DF)
-Determine the fan speed using the following formulae:
Where: rpm
MOTOR
:from the motor plate or
table_3
D
M
: from
table2
D
F
: from machine
Once the pulleys are adjusted and the belt checked and
tensioned, start the fan motor and record the Amps and
Voltage between the phases :
Using the measured data and
table_3
-Theoretical mechanical power at the fan shaft:
P
meca fan
= P
meca Motor
x
Transmission
P
meca fan
= P
elec
x
meca motor
x
Transmission
P
meca fan
= V x I x
3 x cos
x
meca motor
x
Transmission
This formula can be approximated in this way
P
meca fan
= V x I x 1.73 x 0.85 x 0.76 x 0.9
With the fan “rpm” and t
he mechanical power at the fan
shaft an operating point and the supplied airflow can be
estimated using the fan curves.
CHECKING AIRFLOW AND ESP
Using the fan curves on
page 25, 26, 27
, the airflow, the
total pressure available (P
TOT
) and the corresponding
dynamic pressure (Pd) can now be estimated, for a specific
operating point;
The next step consists in estimating the pressure losses
across the unit.
This can be achieved using the “dirty filter pressure sensor”
and the accessories pressure drop table:
table_4
Also the pressure drop due to the duct inlet into the roof-top
unit can be taken as 20 to 30 Pa.
P
INT
=
P
coil
+
P
Inlet
+
P
Options
using the results from above, the external static pressure
(ESP) can then be estimated:
ESP = P
TOT
- Pd -
P
INT
Table_ 3
Motor information
Motor Size
Nom. Speed
Cos
meca motor
0.75 kW
1400 rpm
0.77
0.70
1.1kW
1429 rpm
0.84
0.77
1.5kW
1428 rpm
0.82
0.79
2.2kW
1436 rpm
0.81
0.81
3.0kW
1437 rpm
0.81
0.83
4kW
1438 rpm
0.83
0.84
5.5kW
1447 rpm
0.83
0.86
7.5kW
1451 rpm
0.82
0.87
Summary of Contents for BAC020SNM
Page 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Page 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Page 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Page 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Page 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Page 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Page 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Page 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Page 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Page 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Page 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Page 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Page 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Page 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Page 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Page 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Page 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...