HEATING: MODULATING GAS BURNER
BALTIC R410A-IOM-0708-E
Page 88
MODULATING GAS (UNDER PATENT INPI Mai 2004)
The actuator
The actuator receives an information 0-10V from the
regulation for the positioning of the air shutter; then
the actuator transmits its position to the printed-board
which will order the valve.
Check position and operation of the actuator
STARTING UP THE GAS BURNER
Purge the pipe-work near the connection on the ignition
control Valve for a few seconds.
-Check that the unit's Treatment Fan Blower is running.
Set the control to “ON” This will priorities the gas burner.
Increase
the
set temperature
(room
set
point
temperature) to a temperature higher than the actual
room temperature.
The start of the gas burner must be done at
high
heat injection
.
Fig. 75
Fig. 78
Bearing surface of the
actuator’s screw
Manual rotation of the
actuator
Disengaging for hand drive
operation
Maximum opening of the actuator
Minimum opening of the actuator
Actuator screw
Fig. 76
Fig. 77
Summary of Contents for BAC020SNM
Page 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Page 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Page 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Page 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Page 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Page 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Page 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Page 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Page 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Page 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Page 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Page 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Page 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Page 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Page 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Page 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Page 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...