CLIMATIC 50 – ROOFTOP – VERSION 23
BALTIC R410A-IOM-0708-E
Page 106
BMS ADRESS TABLES
ModBus, Trend, BACnet & Carel
Logical
@ (hexa) @ (deci)
DS50
01H
1
R/W L [On / Off] Unit
3111
02H
2
R/W L [Reset] Discharges the safety measures of the unit
3112
03H
3
R/W L
[Enable] Stopping and running of the Fan Blower.[Off] the blower is stopped, [On] the
blower is running.
3351
(BMS)
04H
4
R/W L
[Enable] Stopping and running of the fan in the "Control Dead Zone". [Off] the blower
is stopped, [On] the blower is running.
3352
(BMS)
05H
5
R/W L
[BMS] Activation of the Unoccupied mode [Off] Occupied mode - [On] Unoccupied
mode
3935
06H
6
R/W L
[Room regulation] Choices of the priority of regulation in Heating - [Off] Heat Pump
then Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat
Pump
3324
(BMS)
07H
7
R/W L
[F-Air Reheat] Activate reheating of the fresh air in the dead zone to maintain supply
temperature.
3331
(BMS)
08H
8
R/W L
[F-Air Reheat] Choices of the priority of regulation in Heating - [Off] Heat Pump then
Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
3332
(BMS)
09H
9
R/W L [Enable] Run eco: [On] the Economiser is running, [Off] the Economiser if stopped.
3353
(BMS)
0AH
10
R/W L
[Enable] Run CO2 Sensor: [On] Switch-on the CO2 control on a Zone, [Off] Stop the
CO2 control on a zone.
3354
(BMS)
0BH
11
R/W L [Enable] [OFF] Force the unloading of compressors in cooling mode.
3355
(BMS)
0CH
12
R/W L [Enable] [OFF] Force the unloading of compressors in heating mode.
3356
(BMS)
0DH
13
R/W L [Enable] [OFF] Force the unloading of heating module (electric, gas or heat water coil)
3357
(BMS)
0EH
14
R/W L [Enable] [OFF] Force the unloading of humidity control.
3358
(BMS)
0FH
15
R/W L
[Unloaded] Force the stop of half of the compressors moving has the moment of the
activation of this point.
3643
10H
16
R/W L [Clock] [OFF] read hour & minute [ON] write hour & minute
…
11H
17
R/W L [Dry contact] Digital Output, Free 1, BM50-J17-NO12
2141
12H
18
R/W L [Dry contact] Digital Output, Free 2, BE50-J5-NO1
2142
13H
19
R/W L [Dry contact] Digital Output, Free 3, BE50-J6-NO2
2143
14H
20
R/W L [Dry contact] Digital Output, Free 4, BE50-J7-NO3
2144
15H
21
R/W L [Dry contact] Digital Output, Free 5, BE50-J8-NO4
2145
16H
22
R/W L
not used
17H
23
R/W L
not used
18H
24
R/W L
not used
19H
25
R/W L
not used
1AH
26
R/W L
not used
1BH
27
R/W L
not used
1CH
28
R/W L
not used
1DH
29
R/W L
not used
Summary of Contents for BAC020SNM
Page 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Page 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Page 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Page 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Page 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Page 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Page 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Page 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Page 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Page 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Page 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Page 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Page 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Page 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Page 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Page 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Page 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...