background image

Page 8

 5 − Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches of mercury).

During the early stages of evacuation, it is desirable to
close the manifold gauge valve at least once to deter-
mine if there is a rapid rise in 

absolute pressure

. A

rapid rise in pressure indicates a relatively large leak. If
this occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves to
break the vacuum in the line set and indoor unit. Close
the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will void
warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not rise
above 500 microns (29.9 inches of mercury) within a
20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When the absolute pressure requirement above has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of
HCFC-22 refrigerant. Open the manifold gauge valves
to break the vacuum from 1 to 2 psig positive pressure in
the line set and indoor unit. Close manifold gauge valves
and shut off the HCFC-22 cylinder and remove the man-
ifold gauge set.

D − Charging

Units are factory-charged with the amount of HCFC−22 re-
frigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 15
feet (4.6 m) line set. For varying lengths of line set, refer to
table 4 for refrigerant charge adjustment.

TABLE 4

Refrigerant Charge per Line Set Lengths

Liquid Line

Set Diameter

Oz. per 5 ft. (g per 1.5 m) adjust

from 15 ft. (4.6 m) line set*

3/8 in. (9.5 mm)

3 ounce per 5 ft. (85 g per 1.5 m)

NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. The method of charging is determined
by the unit’s 

refrigerant metering device

 and the 

outdoor

ambient temperature

.

Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:

1. Connect the manifold gauge set to the service valves:

low pressure gauge to 

vapor 

valve service port

high pressure gauge to 

liquid 

valve service port

2. Close manifold gauge set valves. Connect the center

manifold hose to an upright cylinder of HCFC−22.

3. Set the room thermostat to call for heat. This will create

the necessary load for properly charging the system in
the cooling cycle.

4. Use a digital thermometer to record the outdoor ambi-

ent temperature.

5. When the heating demand has been satisfied, switch

the thermostat to cooling mode with a set point of 68

F

(20

C). When pressures have stabilized, use a digital

thermometer to record the liquid line temperature.

6. The outdoor temperature will determine which charg-

ing method to use. Proceed with the appropriate charg-
ing procedure.

Charge Using Weigh−in Method (RFC/TXV Sys-
tems) − Outdoor Temp. <65°F (18°C)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, use the weigh−in method to charge the
unit. Do this after any leaks have been repaired.

1. Recover the refrigerant from the unit.
2. Conduct a leak check, then evacuate as previously out-

lined.

3. Weigh in the charge according to the total amount

shown on the unit nameplate.

If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other proce-
dures outlined below.

Summary of Contents for 13ACD Series

Page 1: ...jury or loss of life Installation and service must be performed by a qualified installer or service agency WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered re...

Page 2: ...um overcurrent protection amps 15 20 30 30 45 40 60 3 Minimum circuit ampacity 10 7 14 1 18 7 19 1 25 9 25 7 33 3 Compressor Rated load amps 7 7 10 4 14 1 14 4 19 2 19 2 26 1 p Power factor 98 96 96 9...

Page 3: ...2 Dual Capacitor C12 The compressor and fan in 13ACD series units use per manent split capacitor motors The capacitor is located inside the unit control box see figure 2 A single dual capacitor C12 i...

Page 4: ...ll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 5 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 5 2 As the orbitin...

Page 5: ...beginning electrical service procedures DANGER FAN CONDENSER FAN MOTOR AND COMPRESSOR ACCESS Remove 7 screws REMOVE 7 SCREWS SECURING FAN GUARD REMOVE FAN GUARD FAN ASSEMBLY MOTOR FAN GUARD WIRING FI...

Page 6: ...tem cap stem Use Adjustable Wrench To open rotate Stem Clockwise 90 To close rotate Stem Counter clockwise 90 ball shown open to outdoor coil to indoor coil Service Valve Valve Closed Schrader valve o...

Page 7: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maxi mum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the v...

Page 8: ...er and remove the man ifold gauge set D Charging Units are factory charged with the amount of HCFC 22 re frigerant indicated on the unit rating plate This charge is based on a matching indoor coil and...

Page 9: ...t be used if ambient tem peratures are below 65 F For best results indoor tempera ture should be 70 F 21 C to 80 F 26 C 1 Restrict the airflow see figure 10 through the outdoor coil to achieve pressur...

Page 10: ...5 153 79 157 81 152 77 164 77 75 24 166 81 173 80 167 77 170 76 167 80 170 81 165 77 177 78 80 27 180 82 187 81 181 78 186 76 182 80 184 82 179 78 192 78 85 29 195 82 218 82 195 78 201 77 198 81 198 8...

Page 11: ...coil reinstall the mesh screen by positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose...

Page 12: ...he thermostat 2 24VAC from indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 a...

Reviews: