background image

Page 10

Checking Charge Using Normal Operating Pressures

IMPORTANT

Use table 8 to help perform maintenance checks.
Table 8 is not a procedure for charging the system. Mi-
nor variations in these pressures may be due to differ-
ences in installations. Significant deviations could
mean that the system is not properly charged or that
a problem exists with some component in the system.

TABLE 7

Approach Values

13ACD Model

−018

−024

−030

−036

−042

−048

−060

Temp. °F (°C)

6 (3.3)

10 (5.6)

11 (6)

9 (5)

6 (3.3)

6 (3.3)

8 (4.4)

Approach Value is the Liquid Line Temperature minus Outdoor Ambient Temperature [ºF (ºC) +

 

1ºF (0.5ºC)]

NOTE − For best results, use the same digital thermometer to check both outdoor ambient and liquid temperatures.

TABLE 8

Normal Operating Pressures In psig (liquid and s/− 2 psig)*

Normal Operating Pressures

13ACD

Model

−018

−024

−030

−036

−042

−048−1, −2

units

−048

−060

Values below are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the
pressures to vary.

*Temp. 

5

F

(

5

C)

Liquid Line Pressure/Vapor Line Pressure

Expansion Valve (TXV)

65 (18)

141 / 80

147 / 79

141 / 76

145 / 74

143 / 78

145 / 80

140 / 77

151 / 76

70 (21)

154 / 81

159 / 79

154 / 76

157 / 75

153 / 79

157 / 81

152 / 77

164 / 77

75 (24)

166 / 81

173 / 80

167 / 77

170 / 76

167 / 80

170 / 81

165 / 77

177 / 78

80 (27)

180 / 82

187 / 81

181 / 78

186 / 76

182 / 80

184 / 82

179 / 78

192 / 78

85 (29)

195 / 82

218 / 82

195 / 78

201 / 77

198 / 81

198 / 82

192 / 78

207 / 79

90 (32)

209 / 83

202 / 81

210 / 79

217 / 77

215 / 81

214 / 83

209 / 80

223 / 80

95 (35)

222 / 83

234 / 82

227 / 80

234 / 78

231 / 82

230 / 84

227 / 81

240 / 80

100 (38)

244 / 84

251 / 83

249 / 81

251 / 79

249 / 83

247 / 84

243 / 81

259 / 81

105 (41)

258 / 85

267 / 84

260 / 81

268 / 79

268 / 84

265 / 85

261 / 82

277 / 81

110 (43)

276 / 85

287 / 84

278 / 82

288 / 80

287 / 84

283 / 85

279 / 83

297 / 82

115 (45)

294 / 86

307 / 85

299 / 83

309 / 81

308 / 85

303 / 86

296 / 83

318 / 83

Fixed Orifice (RFC)

65 (18)

144 / 73

147 / 68

140 / 66

150 / 67

147 / 70

145 / 70

143 / 73

150 / 67

70 (21)

157 / 76

160 / 71

152 / 68

162 / 70

158 / 72

156 / 72

154 / 75

163 / 70

75 (24)

167 / 78

173 / 74

166 / 71

176 / 72

171 / 75

170 / 75

167 / 78

177 / 72

80 (27)

182 / 80

189 / 77

180 / 74

190 / 74

184 / 77

183 / 78

180 / 79

191 / 75

85 (29)

196 / 82

203 / 79

196 / 76

205 / 76

198 / 78

198 / 80

193 / 81

207 / 77

90 (32)

211 / 84

219 / 81

211 / 79

220 / 78

213 / 80

213 / 82

207 / 82

221 / 79

95 (35)

225 / 84

238 / 83

227 / 80

237 / 79

228 / 81

230 / 84

221 / 84

239 / 80

100 (38)

242 / 86

255 / 85

294 / 82

255 / 80

245 / 82

246 / 85

237 / 85

256 / 81

105 (41)

256 / 86

272 / 86

262 / 83

273 / 81

262 / 84

264 / 86

253 / 86

274 / 83

110 (43)

278 / 88

294 / 87

282 / 84

291 / 83

281 / 84

282 / 87

269 / 87

295 / 84

115 (45)

293 / 88

317 / 88

302 / 86

314 / 84

300 / 85

301 / 88

289 / 88

315 / 85

*Temperature of the air entering the outside coil.

Summary of Contents for 13ACD Series

Page 1: ...jury or loss of life Installation and service must be performed by a qualified installer or service agency WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered re...

Page 2: ...um overcurrent protection amps 15 20 30 30 45 40 60 3 Minimum circuit ampacity 10 7 14 1 18 7 19 1 25 9 25 7 33 3 Compressor Rated load amps 7 7 10 4 14 1 14 4 19 2 19 2 26 1 p Power factor 98 96 96 9...

Page 3: ...2 Dual Capacitor C12 The compressor and fan in 13ACD series units use per manent split capacitor motors The capacitor is located inside the unit control box see figure 2 A single dual capacitor C12 i...

Page 4: ...ll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 5 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 5 2 As the orbitin...

Page 5: ...beginning electrical service procedures DANGER FAN CONDENSER FAN MOTOR AND COMPRESSOR ACCESS Remove 7 screws REMOVE 7 SCREWS SECURING FAN GUARD REMOVE FAN GUARD FAN ASSEMBLY MOTOR FAN GUARD WIRING FI...

Page 6: ...tem cap stem Use Adjustable Wrench To open rotate Stem Clockwise 90 To close rotate Stem Counter clockwise 90 ball shown open to outdoor coil to indoor coil Service Valve Valve Closed Schrader valve o...

Page 7: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maxi mum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the v...

Page 8: ...er and remove the man ifold gauge set D Charging Units are factory charged with the amount of HCFC 22 re frigerant indicated on the unit rating plate This charge is based on a matching indoor coil and...

Page 9: ...t be used if ambient tem peratures are below 65 F For best results indoor tempera ture should be 70 F 21 C to 80 F 26 C 1 Restrict the airflow see figure 10 through the outdoor coil to achieve pressur...

Page 10: ...5 153 79 157 81 152 77 164 77 75 24 166 81 173 80 167 77 170 76 167 80 170 81 165 77 177 78 80 27 180 82 187 81 181 78 186 76 182 80 184 82 179 78 192 78 85 29 195 82 218 82 195 78 201 77 198 81 198 8...

Page 11: ...coil reinstall the mesh screen by positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose...

Page 12: ...he thermostat 2 24VAC from indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 a...

Reviews: