I − UNIT COMPONENTS 

13ACD UNIT COMPONENTS

FIGURE 1

OUTDOOR FAN/MOTOR

CONTROL BOX

SUCTION LINE

SUCTION LINE

VALVE

LIQUID LINE

VALVE

DISCHARGE

LINE

COMPRESSOR

A − Control Box (Figure 2)

13ACD units are not equipped with a 24V transformer. All
24 VAC controls are powered by the indoor unit. Refer to
wiring diagram.

Electrical openings are provided under the control box cov-
er. Field thermostat wiring is made to color-coded pigtail
connections.

1 − Compressor Contactor K1

The compressor is energized by a contactor located in the
control box. See figure 2. Single−pole contactors are used
in 13ACD series units. K1 is energized by the indoor ther-
mostat terminal Y1 (24V) when thermostat demand is
present.

DANGER

Electric Shock Hazard.
May cause injury or death.
Line voltage is present at all compo-
nents when unit is not in operation on
units with single pole contactors.
Disconnect all remote electrical power
supplies before opening unit panel.
Unit may have multiple power supplies.

FIGURE 2

DUAL CAPACITOR

(C12)

TIMED OFF

CONTROL

(OPTION)

COMPRESSOR

CONTACTOR

(K1)

13ACD UNIT CONTROL BOX

GROUNDING

LUG

2 − Dual Capacitor C12

The compressor and fan in 13ACD series units use per-

manent split capacitor motors. The capacitor is located

inside the unit control box (see figure 2). A single dual"

capacitor (C12) is used for both the fan motor and the

compressor (see unit wiring diagram). The fan side and

the compressor side of the capacitor have different MFD

ratings. Ratings will be on compressor nameplate and

condenser fan nameplate.

3 − Timed Off Control TOC (option)

The time delay is electrically connected between thermo-
stat terminal Y and the compressor contactor. Between
cycles, the compressor contactor is delayed for 5 minutes 

±

2 minutes but may last as long as 8 minutes. At the end of
the delay, the compressor is allowed to energize. When
thermostat demand is satisfied, the time delay opens the
circuit to the compressor contactor coil and the compressor
is de−energized.

4 − High Pressure Switch (option)

The manual−reset high pressure switch is located in the liq-
uid line. When liquid line pressure exceeds the factory set-
ting of 410 +  10 psi, the switch opens and shuts off the com-
pressor.

5 − Pressure Switch (−1 units only)

The auto−reset pressure switch is located in the suction
line. When suction line pressure drops below the factory
setting of 25 +  5 psi, the switch opens and shuts off the
compressor.

Summary of Contents for 13ACD Series

Page 1: ...jury or loss of life Installation and service must be performed by a qualified installer or service agency WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered re...

Page 2: ...um overcurrent protection amps 15 20 30 30 45 40 60 3 Minimum circuit ampacity 10 7 14 1 18 7 19 1 25 9 25 7 33 3 Compressor Rated load amps 7 7 10 4 14 1 14 4 19 2 19 2 26 1 p Power factor 98 96 96 9...

Page 3: ...2 Dual Capacitor C12 The compressor and fan in 13ACD series units use per manent split capacitor motors The capacitor is located inside the unit control box see figure 2 A single dual capacitor C12 i...

Page 4: ...ll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 5 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 5 2 As the orbitin...

Page 5: ...beginning electrical service procedures DANGER FAN CONDENSER FAN MOTOR AND COMPRESSOR ACCESS Remove 7 screws REMOVE 7 SCREWS SECURING FAN GUARD REMOVE FAN GUARD FAN ASSEMBLY MOTOR FAN GUARD WIRING FI...

Page 6: ...tem cap stem Use Adjustable Wrench To open rotate Stem Clockwise 90 To close rotate Stem Counter clockwise 90 ball shown open to outdoor coil to indoor coil Service Valve Valve Closed Schrader valve o...

Page 7: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maxi mum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the v...

Page 8: ...er and remove the man ifold gauge set D Charging Units are factory charged with the amount of HCFC 22 re frigerant indicated on the unit rating plate This charge is based on a matching indoor coil and...

Page 9: ...t be used if ambient tem peratures are below 65 F For best results indoor tempera ture should be 70 F 21 C to 80 F 26 C 1 Restrict the airflow see figure 10 through the outdoor coil to achieve pressur...

Page 10: ...5 153 79 157 81 152 77 164 77 75 24 166 81 173 80 167 77 170 76 167 80 170 81 165 77 177 78 80 27 180 82 187 81 181 78 186 76 182 80 184 82 179 78 192 78 85 29 195 82 218 82 195 78 201 77 198 81 198 8...

Page 11: ...coil reinstall the mesh screen by positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose...

Page 12: ...he thermostat 2 24VAC from indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 a...

Reviews: