LIQUID LINE

3/8 in. (10 mm)

TABLE 3

Ounce per 5 foot (ml per mm) adjust

from 15 foot (4.5m) line set*

*If line set is greater than 15 ft. (4.5 m) add this amount. If line set

is less than 15 feet (4.5 m) subtract this amount

SET DIAMETER

3 ounce per 5 feet (90 ml per 1524 mm)

Units are designed for line sets up to 50 feet (15.2 m).
Consult Lennox Refrigerant Piping Manual
Corp.9351−L9 and available on the Lennox  DaveNet
web site for line sets over 50 feet (15.2 m).

A − Pumping Down System

CAUTION

Deep vacuum operation (operating compressor
below 0 psig) can cause internal fusite arcing
resulting in a damaged or failed compressor. This
type of damage will result in denial of warranty claim.

The system may be pumped down when leak checking the
line set and indoor coil or making repairs to the line set or
indoor coil. Attach gauge manifold then follow below:

 1− Close liquid line valve.

 2− Start outdoor unit.
 3− Monitor suction gauge. Stop unit when 0 psig is reached.

 4− Close vapor line valve.

B − Leak Testing

After the line set has been connected to the indoor and out-
door units, check the line set connections and indoor unit
for leaks.

WARNING

Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire and
/ or an explosion, that can result in
personal injury or death.

WARNING

Danger of explosion!
When using a high pressure gas such
as dry nitrogen to pressurize a refriger-
ant or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).

Using an Electronic Leak Detector or Halide

 1 − Connect a cylinder of HCFC-22 to the center port of the

manifold gauge set.

 2 − With both manifold valves closed, open the valve on the

HCFC-22 cylinder (vapor only).

 3 − Open the high pressure side of the manifold to allow the

HCFC-22 into the line set and indoor unit. Weigh in a
trace amount of HCFC-22.

 

[A trace amount is a maxi-

mum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.]
Close the valve on the HCFC-22 cylinder and the valve
on the high pressure side of the manifold gauge set.
Disconnect the HCFC-22 cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

 5 − Connect the manifold gauge set high pressure hose to

the vapor valve service port. 

(Normally, the high pres-

sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)

 6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.

 7 − After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and HCFC-22
mixture. Correct any leaks and recheck.

C − Evacuating the System

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

NOTE − This evacuation process is adequate for a new
installation with clean and dry lines. If excessive mois-
ture is present, the evacuation process may be re-
quired more than once.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.

 1 − Connect manifold gauge set to the service valve ports :

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

 3 − Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

 4 − Open both manifold valves and start the vacuum

pump.

Summary of Contents for 13ACD Series

Page 1: ...jury or loss of life Installation and service must be performed by a qualified installer or service agency WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered re...

Page 2: ...um overcurrent protection amps 15 20 30 30 45 40 60 3 Minimum circuit ampacity 10 7 14 1 18 7 19 1 25 9 25 7 33 3 Compressor Rated load amps 7 7 10 4 14 1 14 4 19 2 19 2 26 1 p Power factor 98 96 96 9...

Page 3: ...2 Dual Capacitor C12 The compressor and fan in 13ACD series units use per manent split capacitor motors The capacitor is located inside the unit control box see figure 2 A single dual capacitor C12 i...

Page 4: ...ll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 5 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 5 2 As the orbitin...

Page 5: ...beginning electrical service procedures DANGER FAN CONDENSER FAN MOTOR AND COMPRESSOR ACCESS Remove 7 screws REMOVE 7 SCREWS SECURING FAN GUARD REMOVE FAN GUARD FAN ASSEMBLY MOTOR FAN GUARD WIRING FI...

Page 6: ...tem cap stem Use Adjustable Wrench To open rotate Stem Clockwise 90 To close rotate Stem Counter clockwise 90 ball shown open to outdoor coil to indoor coil Service Valve Valve Closed Schrader valve o...

Page 7: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maxi mum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the v...

Page 8: ...er and remove the man ifold gauge set D Charging Units are factory charged with the amount of HCFC 22 re frigerant indicated on the unit rating plate This charge is based on a matching indoor coil and...

Page 9: ...t be used if ambient tem peratures are below 65 F For best results indoor tempera ture should be 70 F 21 C to 80 F 26 C 1 Restrict the airflow see figure 10 through the outdoor coil to achieve pressur...

Page 10: ...5 153 79 157 81 152 77 164 77 75 24 166 81 173 80 167 77 170 76 167 80 170 81 165 77 177 78 80 27 180 82 187 81 181 78 186 76 182 80 184 82 179 78 192 78 85 29 195 82 218 82 195 78 201 77 198 81 198 8...

Page 11: ...coil reinstall the mesh screen by positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose...

Page 12: ...he thermostat 2 24VAC from indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 a...

Reviews: