M3000 Installation Guide
103
Troubleshooting
• WARNING! •
Do not set JP1 to 12 V for a 5 V reader. permanent damage may result to the
reader.
2.
Be sure that the proper resistor packs are installed in the 2SRP board. Refer to
3.
Check the wiring between the 2SRP board and the reader. Refer to
the reader installation manual.
4.
Be sure the connector is firmly seated in the 2SRP board.
Problem:
The reader has power, but the Badge Read OK LED on the CPU board does not light up
when a badge is presented.
Resolution
:
1.
Be sure the resistor packs are installed and are the correct value for the reader type being used.
2.
Be sure that the switch settings on the 2SRP board for address and reader technology/format are
correct. Refer to
.
3.
Check the wiring between the reader and the 2SRP board. Refer to
and
the reader installation manual.
Using the 8RP Board
Problem:
The reader does not power up.
Resolution
:
1.
Check the wiring between the 8RP board and the reader. Refer to
reader installation manual.
2.
Be sure the connector is firmly seated in the 8RP board.
Problem:
The reader has power, but the Badge Read OK LED on the CPU board does not light up
when a badge is presented.
Resolution
:
1.
Be sure that the switch settings on the 8RP board for address and reader technology/format are
correct. Refer to
.
2.
Check the wiring between the reader and the 8RP board. Refer to
and the
reader installation manual.
Door Strike Problems
Problem:
The Badge Read OK LED lights on the CPU board and the door reader LED lights on the
reader, but the door strike does not operate.
Resolution:
1.
Check the wiring from the door strike to the reader board. In the chapter of the appropriate reader
board, refer to the section that covers wiring the door strike. Also refer to the door strike
manufacturer’s installation instructions.
2.
Be sure the door strike power supply is operating properly.
PXNplus CPU Board Problems
If the problem is not caused by incorrect hardware wirings or settings, check the software settings of
the PXNplus CPU board using the Integrated Configuration Tool.
Problem:
I need to restore the factory default settings.
Summary of Contents for m3000
Page 1: ...7 3 M3000 Installation Guide...
Page 4: ......
Page 14: ...Introduction 14 M3000 Installation Guide...
Page 30: ...Power Communications Board 30 M3000 Installation Guide...
Page 32: ...PXNplus CPU Board 32 M3000 Installation Guide PXNplus CPU Board Layout...
Page 38: ...Reader Processing Boards 38 M3000 Installation Guide 2RP Board Layout 2RP Board Layout...
Page 50: ...Reader Processing Boards 50 M3000 Installation Guide 2SRP Board Layout 2SRP Board Layout...
Page 55: ...M3000 Installation Guide 55 2SRP Board 2SRP Supervised Reader Connector Points...
Page 61: ...M3000 Installation Guide 61 2SRP Board Wiring 2SRP Door Strike Internal Relay...
Page 65: ...M3000 Installation Guide 65 8RP Board Board Layout 8RP Board Layout...
Page 70: ...Reader Processing Boards 70 M3000 Installation Guide...
Page 72: ...Optional DI and DO Boards 72 M3000 Installation Guide 20DI Board Layout 20DI Board Layout...
Page 75: ...M3000 Installation Guide 75 16DO and 16DOR Boards 16DO Board Layout...
Page 76: ...Optional DI and DO Boards 76 M3000 Installation Guide 16DOR Board Layout...
Page 80: ...Pre Power Up Testing 80 M3000 Installation Guide...
Page 99: ...M3000 Installation Guide 99 CE Regulatory Notice CE Regulatory Notice...
Page 100: ...Regulatory Information 100 M3000 Installation Guide...
Page 110: ...110 M3000 Installation Guide...
Page 114: ...114 M3000 Installation Guide Resistances Detected by PXNplus...
Page 117: ...M3000 Installation Guide 117 Index...