M3000 Installation Guide
59
2SRP Board
1.
Follow the installation specifications for the device. Mount the device according to the
manufacturer’s specifications. The alarm device (door contact) should have a dry contact which
can have a Normally Open or Normally Closed type switch. A Normally Closed contact is in its
normal or resting position when it is closed. For example, the contact is closed when the door is
closed. The opposite is true for a Normally Open contact. In this case, the contact is open when
the door is closed.
2.
Select the appropriate digital input for each alarm input device.
3.
Ground the shields of the cable at the M3000 enclosure grounding studs. Insulate the shield (with
tape or shrink tubing) at the DI device end to avoid electrical noise.
4.
Install two (2) end-of-line resistors. Install each resistor as close to the door status contact as
possible.
5.
We recommend the standard 1,000 (1K) ohm, 1/4 watt, 5% tolerance, high-quality end-of-line
resistors. If different resistor values are required, refer to
Appendix B: Termination Resistance
Wiring 2SRP Door Alarm Contact and Exit Request
the resistors.
Supervised DI End-of-line Resistors
for the appropriate switch settings.
6.
Wire the supervised door DI between pin 8 (Door DI) and pin 9 (Door DI Return). Wire the
supervised exit DI between pin 5 (Exit DI) and pin 10 (Exit DI Return). The contact can be
Normally Open or Normally Closed.
• WARNING! •
The supervision capability will be impaired if the resistors are
not
wired
immediately adjacent to the door status contact.
7.
Insulate resistors with tape or heat shrink tubing.
8.
Document how you wired the alarm input devices. Future expansion of the system and its
maintenance depend upon accurate documentation.
Summary of Contents for m3000
Page 1: ...7 3 M3000 Installation Guide...
Page 4: ......
Page 14: ...Introduction 14 M3000 Installation Guide...
Page 30: ...Power Communications Board 30 M3000 Installation Guide...
Page 32: ...PXNplus CPU Board 32 M3000 Installation Guide PXNplus CPU Board Layout...
Page 38: ...Reader Processing Boards 38 M3000 Installation Guide 2RP Board Layout 2RP Board Layout...
Page 50: ...Reader Processing Boards 50 M3000 Installation Guide 2SRP Board Layout 2SRP Board Layout...
Page 55: ...M3000 Installation Guide 55 2SRP Board 2SRP Supervised Reader Connector Points...
Page 61: ...M3000 Installation Guide 61 2SRP Board Wiring 2SRP Door Strike Internal Relay...
Page 65: ...M3000 Installation Guide 65 8RP Board Board Layout 8RP Board Layout...
Page 70: ...Reader Processing Boards 70 M3000 Installation Guide...
Page 72: ...Optional DI and DO Boards 72 M3000 Installation Guide 20DI Board Layout 20DI Board Layout...
Page 75: ...M3000 Installation Guide 75 16DO and 16DOR Boards 16DO Board Layout...
Page 76: ...Optional DI and DO Boards 76 M3000 Installation Guide 16DOR Board Layout...
Page 80: ...Pre Power Up Testing 80 M3000 Installation Guide...
Page 99: ...M3000 Installation Guide 99 CE Regulatory Notice CE Regulatory Notice...
Page 100: ...Regulatory Information 100 M3000 Installation Guide...
Page 110: ...110 M3000 Installation Guide...
Page 114: ...114 M3000 Installation Guide Resistances Detected by PXNplus...
Page 117: ...M3000 Installation Guide 117 Index...