TABLE 8
Battery Current (100% Load) and Minimal Recommended Cable Sections
POWER
BATTERY CURRENT
MINIMAL RECOMMENDED
CABLE SECTION
10 kVA
44A
1 x 10 mm
2
for each pole
15 kVA
66A
1 x 16 mm
2
for each pole
20 kVA
88A
1 x 25 mm
2
for each pole
30 kVA TT/TM
132A
1 x 50 mm
2
for each pole
40 kVA
176A
2 x 25 mm
2
for each pole
60 kVA
264A
2 x 50 mm
2
for each pole