68
®
PM status
Battery X
Voltage
Voltage measured at the ends of the batteries by the power module X [V]
Current
Current required to the batteries from the power module X (negative if the
batteries are being charged) [A]
Batt. Charger
Status of the battery charger inside module X
Misc. X
INV. dissip. Temp. Temperature of the INV dissipater (Inverter) of the power module X [°C]
BST dissip. Temp. Temperature of the Booster /PFC dissipater of the power module X [°C]
Fan speed
Fan speed expressed as a percentage of the power module X
HV Bus pos.
Voltage on the DC BUS positive of the power module X [V]
HV Bus neg.
Voltage on the DC BUS negative of the power module Xm [V]
PM
Historical
Data X
Run Time
Total time working
Batt.Time
Total time running on battery
CarBatt.Time
Total time the battery charger has been working
Bypass int.
Total number of Bypass interventions
Battery int.
Total number of battery interventions
Dumper int.
Total number of Dumper interventions
T mains high
Total number of times the input mains voltage has exceeded the maximum
value allowed by the power module
No.Overheat.
Total number of overheatings
No. Overloads Total number of overloads
No. HV Bus run Total number of overvoltages on the Bus
No. Out DC Level Total number of continuous voltage presences in output from the PMs
7. Control Panel
INDICATION
Press ENTER to change the X value and consequently vary the power module from where you read data.
Diagnostics
(*)
Reset PM
Errors
Deletes the memory of errors found in the power
module. Resets only resettable errors.
PM SW update (*)
Update all
the PMs
It allows the sequential and automatic updating of the internal
software of all the UPS power modules. Press “ENTER” to start the
procedure. If the update is unnecessary the following message
appears on the display:
“PM SW versions updated!” Press “ESC” to exit the frame.
Update a
single
PM
It allows the updating of the internal software of a single power
module. Using the “ARROW” keys you select the module you wish to
update (‘PM00’ indicates the module at the top on the left, going
on to the last one at the bottom on the right).
By pressing “ENTER” key a frame appears that gives a comparison
between the software that is actually in the module selected and
the software you are about to load. Press “ENTER” to start the update
procedure.
Once updated, the message “PM SW version updated!” appears on
the display. Press “ESC” to exit the frame.
(following)
(*) Available in the “Service Mode” only
Summary of Contents for Trimod 10 kVA
Page 1: ...Trimod Operating and Maintenance Manual Part LE05768AA 07 12 01 GF ...
Page 2: ... 2 EN ENGLISH 3 Trimod ...
Page 12: ...12 UPS Trimod 10 UPS Trimod 10 15 20 2 3 Models 2 Technological description ...
Page 13: ...Trimod Operating and Maintenance Manual 13 UPS Trimod 10 15 20 UPS Trimod 30 TT ...
Page 14: ...14 UPS Trimod 30 TM UPS Trimod 40 2 Technological description ...
Page 15: ...Trimod Operating and Maintenance Manual 15 UPS Trimod 60 ...
Page 16: ...16 2 Technological description UPS Trimod BATTERY UPS Trimod BATTERY 2 ...
Page 42: ...42 5 Installation UPS Trimod 30TM ...
Page 43: ...Trimod Operating and Maintenance Manual 43 UPS Trimod 30TT ...
Page 44: ...44 UPS Trimod 40 60 5 Installation ...
Page 46: ...46 5 Installation ...