![LEGRAND Trimod 10 kVA Operating And Maintenance Manual Download Page 38](http://html.mh-extra.com/html/legrand/trimod-10-kva/trimod-10-kva_operating-and-maintenance-manual_1872200038.webp)
38
®
The connection of a Trimod® BATTERY to the UPS Trimod® 40 - 60 must be done accoring to the diagram above and the
steps listed below:
1. Make sure that all the battery fuse carrier isolating switches are open;
2. In each Trimod® BATTERY remove the lower front panel;
3. In each Trimod® BATTERY remove the terminal block loosening the 2 securing screws;
4. Connect the UPS and the additional battery cabinet using the earth cable (yellow-green);
5. Use the wirings supplied with the Trimod® BATTERY to connect the positive and negative terminals of the UPS Trimod®
to those of the Trimod® BATTERY.