Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is
not followed.
This symbol points out the instructions, which may result with injury of the
operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
Description of the Symbols Used in the Manual
UPS: Uninterruptible Power Supply
ESD: Emergency Switching Device
RS232: Serial Communication Protocol
RS485: Serial Communication Protocol
MODBUS: Modicon Communication Protocol
SNMP: Simple Network Management Protocol
V: Volt
A: Ampere
P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit
Breaker;
“ON”: Closing the Circuit
“OFF”: Opening the Circuit
KEOR T EVO
Installa
tion & Oper
ation M
anual
Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is
not followed.
This symbol points out the instructions, which may result with injury of the
operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
Description of the Symbols Used in the Manual
UPS: Uninterruptible Power Supply
ESD: Emergency Switching Device
RS232: Serial Communication Protocol
RS485: Serial Communication Protocol
MODBUS: Modicon Communication Protocol
SNMP: Simple Network Management Protocol
V: Volt
A: Ampere
P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit
Breaker;
“ON”: Closing the Circuit
“OFF”: Opening the Circuit
61
59
KEOR T EVO
Installa
tion & Oper
ation M
anual
8.4.
Dry Contacts
There are 4 dry contact sockets on the Interface Board. The relays can be programmable from Relay
Functions menu (under
Settings
menu). “General alarm, Input failure, Battery failure, Output failure, Bypass
active, Output overload, High temperature” alarms can be assigned to the contacts. Each alarm can be
assigned to separate relays but also one alarm may be assigned to all relays.
Each output socket 3-pin and middle pin is
fix
ed, the upper pin is normally closed and lower pin is normally
open.
You may see the relay numbers as above.
Maximum voltage to be applied to the relay contacts is 42VAC rms (sinus) or
60VDC. Maximum contact current depends on the applied voltage and the
load characteristic. Both maximum voltage and maximum contact current
corresponding to the applied voltage shall not be exceeded.
Free contact relay connection cables shall have a cross-section of 1.5 mm
2
.
Maximum allowed resistive contact currents for several voltages are given on the table below:
Each relay has both a normally open (NO) and a normally closed (NC) contact. One end of these contacts
is common.
Relay functions are described below:
Relay functions can be changed through front panel.
Applied voltage
Maximum contact current for resistive load
Up to 42 VAC
16 A
Up to 20 VDC
16 A
30 VDC
6 A
40 VDC
2 A
50 VDC
1 A
60 VDC
0.8 A
Table.10
Relay
Default Function
Relay 1
General Alarm
Relay 2
Input failure
Relay 3
Battery failure
Relay 4
Output failure
Table.11