Keor MOD
Installa
tion and main
tenanc
e manual
73
During the hot-swap procedure the maximum active power available is indicated in the following table:
MAXIMUM ACTIVE POWER AVAILABLE
KEOR MOD 50
25 kW (50%)
KEOR MOD 75
50 kW (66%)
KEOR MOD 100
75 kW (75%)
KEOR MOD 125
100 kW (80%)
KEOR MOD 150
125 kW (84%)
KEOR MOD 175
150 kW (86%)
KEOR MOD 200
175 kW (88,5%)
KEOR MOD 225
200 kW (89%)
KEOR MOD 250
225 kW (90%)
The following is the how-swap procedure:
1. Check that the load connected to the UPS allows the power module replacement without causing an overload.
2. On the main screen, tap on the UPS which has the PM to replace.