Archimod®
Oper
ating and main
tenanc
e manual
17
3 104 51
3 104 52
3 104 53
3 104 54
3 104 55
3 104 56
3 104 57
Command board
1
2
3
Redundacy of command board
No
Yes
Percentage of load admitted
after rupture of a control board
-
50%
66%
(50÷75)%
(60÷80)%
66%
Model
20 kVA
40 kVA
60 kVA
80 kVA
100 kVA
120 kVA
Power Module PM7
3 PM7
driven
by control
board N.1
3 PM7
driven
by control
board N.1
3 PM7
driven
by control
board N.1
6 PM7
driven
by control
board N.1
6 PM7
driven
by control
board N.1
6 PM7
driven
by control
board N.1
3 PM7
driven
by control
board N.2
3 PM7
driven
by control
board N.2
6 PM7
driven
by control
board N.2
6 PM7
driven
by control
board N.2
3 PM7
driven
by control
board N.2
3 PM7
driven
by control
board N.3
3 PM7
driven
by control
board N.3
3 PM7
driven
by control
board N.3
6 PM7
driven
by control
board N.3
Maximum output power during
replacement mode Hot
swappable modules
-
50%
66%
(50÷75)%
(60÷80)%
66%
Maximum output power in case of
failure of a module (Redundancy)
0% (with
3 fhase
load)
50%
66%
75%
80%
84%
66% (with
single
fhase load)
Power Module PM7
3
6
9
12
15
18
Characteristics
of Power Module PM7
Nominale Power 6.7kVA
Active Power 5.4kW
Hot swappable electronics is permitted by dedicated procedure,
replacing a power module with the machine on after turning off,
via the relative control board, its corresponding 3-phase block
(3 or 6 power modules).
Number of Display
1
2
3
Characteristics of Display
NON Hot
Swappable
Redundant.
Independent displays each connected
with a separate command.
Display back light green background
Multicolor Status Indicator operation (green / yellow / red)
RS232 user port
N.1
Rear side
N.2
Rear side
N.3
Rear side
RS232 maintenance port
N.1
Front side
N.2
Front side
N.3
Front side
Contact port
N.1 DB15
rear side
N.2 DB15
rear side
N.3 DB15
rear side
Functional electrical characteristics
(continue)
Summary of Contents for Archimod
Page 1: ...Archimod Operating and Maintenance Manual Part LE05755AA 09 12 01 GF ...
Page 2: ...Archimod 2 EN ENGLISH 3 ...
Page 14: ...14 3 Technical description UPS Archimod 60 UPS Archimod 80 UPS Archimod 100 ...
Page 15: ...Archimod Operating and maintenance manual 15 UPS Archimod 120 UPS Archimod Battery ...
Page 81: ...81 Archimod ...
Page 82: ...82 ...
Page 83: ......