Mains output connection
Before connecting the output make certain the UPS is off and there is no voltage on the output disconnector terminals.
- Connect the output line earth cable to the terminal on the base of the equipment.
- Connect the output line Neutral cable to its terminal on the output disconnector using a suitable cable terminal.
- Connect cables L1,L2, L3 one by one of the output line to their terminals L1out, L2out and L3out on the output
disconnector using suitable cable terminals and taking care to observe correct cyclicity of the phases L1, L2 and L3.