8. Diagnostics
MESSAGE
MEANING
Inverter failure
Failure occurred in the Inverter circuit.
Booster failure
Failure occurred in the Booster / PFC circuit.
Battery charger failure
Failure occurred in the Battery Charger circuit.
Overheating
Overheating. Check the UPS ventilation system.
Overload
Overload. Check the load level connected to the UPS.
Excessive voltage on the H.V. BUS
Anomalous high voltage on the DC BUS.
Excessive DC level in output
The DC (Direct Current) level in output is excessive.
Excessive battery voltage
Battery voltage too high.
Power module communication failure
Failure of the communication system with the Power Modules.
Emergency
Emergency.
Load not powered.
Power to the loads has been interrupted.
Abnormal shutting down
UPS shut down abnormally
Shutting down due to an overload
UPS shut down due to an prolonged overload.
Shutting down due to
an Emergency Power Off
UPS shut down due to an Emergency Power Off.
Batteries KO
Battery failure.
PM battery connection failure
Failure in the connection of the batteries to the Power Module. Check
battery fuses and wiring.
PM mains connection failure
Failure in the connection of power to the Power Module. Check mains
fuses and wiring.
PM HVBus connection failure
Failure in the HVBus connection with the Power Modules. Check the
HVBus fuses inside the Power Modules.
Communication failure between CM
Communication error between commands.
IMPORTANT EVENTS
Summary of Contents for Archimod
Page 1: ...Archimod Operating and Maintenance Manual Part LE05755AA 09 12 01 GF ...
Page 2: ...Archimod 2 EN ENGLISH 3 ...
Page 14: ...14 3 Technical description UPS Archimod 60 UPS Archimod 80 UPS Archimod 100 ...
Page 15: ...Archimod Operating and maintenance manual 15 UPS Archimod 120 UPS Archimod Battery ...
Page 81: ...81 Archimod ...
Page 82: ...82 ...
Page 83: ......