56
®
7. Control panel
Historical Data
UPS operation
Total time the UPS has been working
With battery
Total time the UPS has been running on battery
Battery charger Op.
Total time the battery charger has been working
Tot. run downs
Total number of times the batteries have been completely run down
Booster Int.
Total number of Booster interventions
Bypass Int.
Total number of Bypass interventions
Batt. Calibr.
Total number of battery Calibrations
Battery ch.Cycles
Total number of battery charger cycles
Batt.eq.cycles
Total number of battery equalisation cycles
>80% load N
Total number of times the load has exceeded 80%
of nominal load
>80% load T
Total time the load has exceeded 80%
of the nominal load
>100% load N
Total number of times charging has exceeded 100%
of nominal load
>100% load T
Total time the load has exceeded 100%
of the nominal load without the overload being signalled
Options
Startup with Battery If enabled, it allows the UPS to be started when there is a power failure
Restart
If enabled, it allows automatic restarts
Output
Voltage
It sets the output voltage value [V]
Frequency
It sets the output frequency value [Hz]
- Rated Value: it allows the output frequency value to be set (50 or 60
[Hz]) regardless of the supply voltage frequency.
- Automatic Select.: if enabled the UPS measures the input voltage
frequency and synchronises the output to the same value. If disabled
the UPS uses the Nominal Value as the setting.
Inverter (*)
It sets the output configuration and the load applied
- Single-phase: just one single-phase output
- Three-phase 120°: three-phase output suitable
for supplying three-phase loads (e.g. a motor)
- Three separate phases: three single-phase output lines
separate from each other
Phases in
start-up (**)
Phase L1
It allows the UPS start-up status to be programmed
for each output:
- Always on: phase always on in start-up;
- Always off: phase always off in start-up;
- Last status: phase restored to the status prior
to shutting down
Phase L2
Phase L3
7.2.2 UPS settings
(*) Available in the “Service Mode” only (**) only available with the inverter configured with 3 independent phases
ATTENTION:
Please refer to paragraph 2.4 to set the CONFIG INVERTER parameter correctly.
Summary of Contents for Archimod
Page 1: ...Archimod Operating and Maintenance Manual Part LE05755AA 09 12 01 GF ...
Page 2: ...Archimod 2 EN ENGLISH 3 ...
Page 14: ...14 3 Technical description UPS Archimod 60 UPS Archimod 80 UPS Archimod 100 ...
Page 15: ...Archimod Operating and maintenance manual 15 UPS Archimod 120 UPS Archimod Battery ...
Page 81: ...81 Archimod ...
Page 82: ...82 ...
Page 83: ......