Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
45
TECHNICAL CHARACTERISTICS
Outputs OUT2, OUT4 and OUT6: terminals 56-57, 59-60 and 62-63
Contact type
3 x 1 NO
Rating
AC1 – 8A 250V~
AC15 -1,5A 250V~
Maximum usage voltage
300V~
Electrical/mechanical time
1x107 / 1x10
5
operations
Maximum current on terminals 55, 59 and 62
12A
Outputs OUT7, OUT9, OUT10 and OUT 11: terminals 19-21, 30-32, 33-35 and 36-38
Contact type
1 in scambio
Rating
AC1 – 8A 250V~ DC1 – 8A 30V=
AC15 -1,5A 250V~
Maximum usage voltage
300V~
Electrical/mechanical time
1x107 / 1x10
5
operations
Static output OUT 8
Output type
NO
Voltage range
10 – 30V=
Maximum current
50mA
Insulation voltage
AC power
Rated insulation voltage
Ui 250V~
Rated impulse withstand voltage
Uimp 7,3kV
Operating freuency withstand voltage
3kV
Voltmeter inputs Line 1, Line 2 and Line 3
Rated insulation voltage
Ui 600V~
Rated impulse withstand voltage
Uimp 9,8kV
Operating freuency withstand voltage
5,2kV
Uscite OUT1-2, OUT3-4, OUT5-6
Rated insulation voltage
Ui 250V~
Rated impulse withstand voltage
Uimp 7,3kV
Operating freuency withstand voltage
3kV
Uscita OUT7, OUT9, OUT10, OUT11
Rated insulation voltage
Ui 250V~
Rated impulse withstand voltage
Uimp 7,3kV
Operating freuency withstand voltage
3kV
Uscite SSR OUT8
Operating freuency withstand voltage
1kV
RS485 serial interface
Towards Line
1-2-3 inputs
Towards relay outputs
and AC supply
Towards DC logic
Rated impulse withstand voltage
Uimp 9,8kV
Uimp 7,3kV
Uimp 7,3kV
Operating freuency withstand voltage
5,2kV
3kV
3kV