Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
27
M11 - AUTOMATIC TEST
UNIT
DEFAULT
RANGE
P11.01
➊
Automatic TEST enable group 1
OFF
OFF / ON
P11.02
➊
Automatic TEST enable group 2
OFF
OFF / ON
P11.03
➊
Automatic TEST enable group 3
OFF
OFF / ON
P11.04
➊
Interval between TESTS
gg
7
1-60
P11.05
➊
Enable TEST for Monday
ON
OFF / ON
P11.06
➊
Enable TEST for Tuesday
ON
OFF / ON
P11.07
➊
Enable TEST for Wednesday
ON
OFF / ON
P11.08
➊
Enable TEST for Thursday
ON
OFF / ON
P11.09
➊
Enable TEST for Friday
ON
OFF / ON
P11.10
➊
Enable TEST for Saturday
ON
OFF / ON
P11.11
➊
Enable TEST for Sunday
ON
OFF / ON
P11.12
➊
TEST start hour
h
12
00-23
P11.13
➊
TEST start minutes
min
00
00-59
P11.14
➊
TEST time
min
10
1-600
P11.15
➊
Automatic TEST with load switching
OFF
OFF
Load
Dummy load
➊
These parameters are also accessible with user level password.
P11.01 - P11.02 - P11.03 - This activate execution of the periodical test of the respective three gensets.
P11.04 - Interval time between one periodical test and the next. If the test is not enabled on the period expiration date,
the interval will be extended as a consequence to the following enabled day.
P11.05…P11.11 This enables automatic test execution in the single days of the week. OFF means that the test will not be
performed on that day. Caution: The clock must be set correctly.
P11.12 - P11.13 This establishes the date and minutes from the beginning of the periodical test. Caution: The clock must
be set correctly.
P11.14 - Periodical test time in minutes.
P11.15 – Load management during periodical test execution: OFF = The load is not transferred. Load = This enables load
transfer to the genset. Dummy load = This applies the dummy load while the system load is not switched.
M12– DIGITAL INPUTS
(INPn, n=1…20)
UNIT
DEFAULT
RANGE
P12.n.01
INPn input function
(miscellaneous) (see Input functions
table)
P12.n.02
Function index (x)
OFF
OFF / 1…99
P12.n.03
Contact type
NO
NO/NC
P12.n.04
Closing delay
sec
0.05
0.00-600.00
P12.n.05
Opening delay
sec
0.05
0.00-600.00
Note: This menu is divided into 20 sections for each programmable digital input INP1..INP20.
The inputs on the basic board are numbered from INP1 to INP12, while the remaining number refer to the
expansion module inputs.
P12.n.01 - Selection input function selection (see
programmable input function table
).
P12.n.02 - Index possibly associated to the function programmed under the previous parameter. Example: If the input
function is set to
Control menu execution Cxx
and this input must execute control C.07 in the command menu,
then P12.n.02 is set to value 7.
P12.n.03 - Contact type selection: NO normally open or NC normally closed.
P12.n.04 - Selected input contact closing delay.
P12.n.05 - Selected input contact opening delay.