Three-Sources Management System
(T.S.M.S.)
Installa
tion and user manual
33
2.22
Alarms table
The following table shows the alarm codes, together with a description and the default properties of each one.
CODE
DESCRIPTION
ENABLED
A
UT ONL
Y
RE
TAINING
ALL.
GL
OB
. A
ALL.
GL
OB
. B
BL
OCK Q1
BL
OCK Q2
BL
OCK Q3
SIREN
NO L
CD
A01
Battery voltage too low
●
●
●
●
A02
Battery voltage too high
●
●
●
●
A03
QQ1 breaker timeout
●
●
●
●
●
●
A04
QQ2 breaker timeout
●
●
●
●
●
●
A05
QQ3 breaker timeout
●
●
●
●
●
●
A06
Incorrect phase sequence Line .SQ1
●
●
●
●
A07
Incorrect phase sequence Line .SQ2
●
●
●
●
A08
Incorrect phase sequence Line .SQ3
●
●
●
●
A09
Load timeout not powered
●
●
●
●
A10
Local battery charger failure
●
●
●
●
A14
Emergency
●
●
●
●
A15
Q1 breaker protection trip
●
●
●
●
●
●
●
A16
Q2 breaker protection trip
●
●
●
●
●
●
●
A17
Q3 breaker protection trip
●
●
●
●
●
●
●
A18
Q1 breaker withdrawn
●
●
●
●
●
●
●
A19
Q2 breaker withdrawn
●
●
●
●
●
●
●
A20
Q3 breaker withdrawn
●
●
●
●
●
●
●
A21
SQ1 genset line not available
●
●
●
A22
SQ2 genset line not available
●
●
●
A23
SQ3 genset line not available
●
●
●
A24
Maintenance hours SS.Q1
●
●
A25
Maintenance hours S.Q2
●
●
A26
Maintenance hours S.Q3
●
●
A27
Maintenance operations Q1
●
●
A28
Maintenance operations Q2
●
●
A29
Maintenance operations Q3
●
●
A30
Auxiliary voltage breaker alarm
●
●
●
A31
Non-priority load breaker timeout
●
●
●
●
●
A32
Tie breaker CQC1 timeout
●
●
●
●
●
●
●
●
A33
Tie breaker QCC2 timeout
●
●
●
●
●
●
●
●
A34
NPL (Non-Priority-Load) breaker protection trip
●
●
●
●
●
●
●
A35
C1 tie breaker protection trip
●
●
●
●
●
●
●
A36
C2 tie breaker protection trip
●
●
●
●
●
●
●
A37
NPL (Non-Priority-Load) breaker withdrawn
●
●
●
●
●
●
A38
QCC1 tie breaker withdrawn
●
●
●
●
●
●
A39
QCC2 tie breaker withdrawn
●
●
●
●
●
●
UA1…UA8 User alarms