BILS-10003 rev E
43
800
Battery removal / replacement
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries in the UPS, replace with the same number and type of battery
originally supplied in the UPS.
Enersys NP18-12BFR (Legacy Part Number BAT-0373)
C&D Technologies UPS12-140 (Legacy Part Number BBAT-0065)
Enersys NP33-12 (Legacy part number BBAT-0065)
C&D Technologies UPS12-150MR (Legacy Part Number BBAT-10031)
Panasonic LC-LA1233P
Power Battery TC-1235L or PRC-1235L
When replacing batteries in the battery cabinet, replace with the same number and type of
battery originally supplied in the battery cabinet
.
Enersys NP18-12BFR (Legacy Part Number BAT-0373)
C&
D Technologies UPS12-140 (Legacy Part number BBAT-0065)
C&D Technologies UPS12-150MR (Legacy Part Number BBAT-10031)
Enersys NP33-12 (Legacy part number BBAT-0065)
C&D Technologies UPS12-270 (Legacy Part number BBAT-0103)
C&D Technologies UPS12-300MR (Legacy Part Number BBAT-10032)
C&D Technologies UPS12-310 (Legacy Part number BBAT-0122)
C&D Technologies UPS12-350MR (Legacy Part Number BBAT-10033)
801
Battery safety / cautions
Important Safety instructions – save these instructions
CAUTION:
Wear protective clothing and eye wear.
CAUTION:
Batteries can present a risk of electrical shock or burn from high short circuit
current. Observe proper precautions.
CAUTION:
Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
CAUTION:
Never dispose of batteries in a fire. The batteries may explode.
CAUTION:
Never open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes, and may be extremely toxic.
The following precautions should be observed when working on batteries:
-
Remove watches rings and other metal objects.
-
Use tools with insulated handles.
-
Wear rubber gloves and boots.
-
Do not lay tools or metal parts on top of batteries.
-
Determine if the battery is inadvertently grounded. If so remove the source of ground.
Contact with any part of the grounded battery could result in electrical shock.