BILS-10003 rev E
34
Parameter
Sample
Value
Password
Level
Description
35 Charger Amps
06.7
Level 2
Actual measured battery charger output current of Herytage UPS
battery charger.
36 Inverter Amps
000
Level 2
Actual measured battery current when running on battery power.
37 Sensitivity
25
Level 2
Determines the sensitivity of the Herytage UPS.
38 Glitch Count
1 to 5
Level 2
Determines the sensitivity of the Herytage UPS.
39 GFE
NA
Level 2
only used in calibration process – by factory trained personnel.
40 Shutdn Inhib
0,1
Level 2
only used in calibration process – by factory trained personnel.
41 Runtime a
3.7
NP*
Variable used In calculation of Runtime – Do Not Change
42 Runtime b
1931
NP*
Variable used In calculation of Runtime – Do Not Change
43 Runtime c
42922
NP*
Variable used In calculation of Runtime – Do Not Change
44 Runtime d
Level 2
Variable used In calculation of Runtime to indicate AH rating of total
battery pack. The formula is based on the number of 33 amp hour
strings times the number of cells in one string. The factory default for
standard batteries should be:
2k = 13, 3k and 4k = 24, 6k = 36, 8k = 48, 10k = 60, 16k = 109, 20k =
136.
For other battery configurations calculate the setting as:
2, 3, 4k = 24 x (total Amp Hours / 33)
6k = 36 x (total Amp Hours / 33)
8k = 48 x (total Amp Hours / 33)
10k = 60 x (total Amp Hours / 33)
16k = 48 x (total Amp Hours / 33)
20k = 60 x (total Amp Hours / 33)
45 Runtime e
80
NP*
Variable used In calculation of Runtime – Do Not Change
46 Runtime
Varies
NP*
Displays battery time remaining – only when on battery power
47 CF-Vin-M
Varies
Level 2
Calibration Factor for AC Volts In. Value varies with unit
48 CF-Vin-L
Varies
Level 2
Calibration Factor for AC Volts In. Value varies with unit
49 CF-Vout-M
Varies
Level 2
Calibration Factor for AC Volts Out. Value varies with unit
50 CF-Vout-L
Varies
Level 2
Calibration Factor for AC Volts Out. Value varies with unit
51 CF-Aout-M
Varies
Level 2
Calibration Factor for AC Amps Out. Value varies with unit
52 CF-Aout-L
Varies
Level 2
Calibration Factor for AC Amps Out. Value varies with unit
53 CF-DCV-M
Varies
Level 2
Calibration Factor for DC Volts. Value varies with unit
54 CF-DCV-L
Varies
Level 2
Calibration Factor for DC Volts. Value varies with unit
55 CF-Ainv-M
Varies
Level 2
Calibration Factor for DC Amps on Inverter. Value varies with unit