BILS-10003 rev E
12
name plate – if it differs from the power you have available in your building call Legacy
Power Conversion customer service.
Table 301-1 Circuit breaker minimum requirements (Soft-wired installations)
Model
Input Voltage
Line Cord Option
1
Minimum
Circuit Breaker
Requirements
2kVA / 1.6kW
120
120
208
240
C, I
J, E
O, K, L
O, K, L
20A
30A, 50A
15A
15A
3kVA / 2.4kW
120
208
240
J, E
K, L
O, K, L
30A
20A
15A
4kVA / 3.2kW
120
208
240
E
L, M
L, M
50A
30A
30A
6kVA / 4.8kW
120
208
240
NA
N, P
N, P
60A
40A
40A
1
Line Cord Designators: C = 5-20P, I = L5-20P, J = L5-30P, E = 5-50P, O = 6-15P, K = L6-20P, L = L6-30P,
M = L14-30P, N = 6-50P, P = L6-50P
Figure 301-1
- 2kVA - 6kVA soft-wired installation overview
Herytage UPS
Bypass Receptacles