BILS-10003 rev E
33
Parameter
Sample
Value
Password
Level
Description
17 Vin spike max
Level 1
Displays the Highest peak voltage spike measured on the input
power to the UPS since last reset.
– to reset, install password, display parameter, and press clear
18 Vin Nom Set
120
208
240
Level 2
Nominal input voltage
19 Vin High Set
120=138
208=240
240=275
Level 2
Input RMS voltage that causes UPS to go to battery power ; also
recorded as a surge in parameter #11
20 Vin Spike Set
120=300
208=500
240=500
Level 1
Input peak voltage that will record as a spike in parameter # 13
21 Vout Low Set
110
Level 2
Set-point at which low AC output alarm occurs – UPS will shut down
if this set-point is exceeded
22 Vout High Set
130
Level 2
Set-point at which high AC output alarm occurs – UPS will shut down
if this set-point is exceeded
23 Date
09/21/07
Level 1
Current Date (Month / Day / Year)
24 Time
14:43
Level 1
Current Time (24 hour format)
25 Alarm Mask 1
192
Level 1
Allows you to program which alarms activate the dry contact for
remote signaling, sound beeper and alarm light
26 Alarm Mask 2
255
Level 1
Allows you to program which alarms activate the dry contact for
remote signaling, sound beeper and alarm light.
27 Alarm Mask 3
110
Level 1
Allows you to program which alarms activate the dry contact for
remote signaling, sound beeper and alarm light
28 Model
Level 2
Tells microprocessor what size UPS system to be.
29 Auto Restart
0,1
Level 1
Determines if the Herytage UPS will automatically restart after a low
battery condition when AC line returns, or if the system will start when
the key / switch is turned on – if set to no, you must start the
Herytage by programming parameter Number 00 System Mode
0=No, 1=Yes
30 Password
0000,
0001
none
Password Level 0 = All parameters are display only
Password Level 1= Parameters noted as Password Level 1 can be
programmed. To change to level 1 program parameter 30 to 0877.
Parameter 30 will then show 30 Password 0001. To remove or reset
password press program then enter (0000) with parameter #30
displayed
31 Clear logs
Level 1
Press
clear
with this parameter displayed to clear event logs – level
1 password must be entered in parameter # 30 first
32 Software Ver
H15
NP*
Displays the software version installed within the control board
33 Batt.Volts
091.7
Level 2
Actual measured voltage of the Herytage UPS batteries.
34 Charger Mode
0 or 1
Level 1
Allows the user to change charger modes.
0= Off
1= On