61
The barrier does not hinge
(does not rise)
The opening speed is too slow
Increase converter setting
00.013
See Ҥ9.5 Adjusting the
frequency converter”
The boom comes up against
the barrier cover
Check the cover and unhinging
cam fixings
The barrier closes when a
vehicle is front of the IR cell
(or ultrasound) or on the
safety loop
The vehicle is not detected
Check the wiring of the safety
device in question
The barrier does not close
after the passage over the
safety loop
Closing after passage is not
activated
Activate the closing after
passage by creating a shunt
between terminals 7 and 8 on
the terminal board.
The barrier does not close at
the end of the time delay
Closing after time delay is not
activated
Activate the closing after time
delay by creating a shunt
between terminals 9 and 10 on
the terminal board.
The barrier does not remain
open
Automatic closing (after
passage or time delay) is
activated
Remove the shunt(s) between
terminals 7, 8, 9 and 10 on the
terminal board
The barrier does not open
automatically under lack of
voltage
There is not enough
compensation
Increase the compensation
See Ҥ9.4 Adjusting the
compensation”
The barrier does not reach
the horizontal position
There is too much
compensation
Decrease the compensation
See Ҥ9.4 Adjusting the
compensation”
The torque hold must be
delayed slightly to reach the
closing stop
Increase converter setting
00.022
See Ҥ9.5 Adjusting the
frequency converter”
The traffic light does not
come on or remains fixed
The cable is disconnected
Reconnect the cable
The traffic light is broken
Replace the traffic light
The relay operating the light is
broken
Replace the relay
The siren does not sound
The cable is disconnected
Reconnect the cable