INSTALLATION AND MAINTENANCE MANUAL
47
Power supply protection device
nominal current (US)
Min phase conductor
section in mm
2
(AWG)
Min Protection conductor
section in mm
2
(AWG)
Automatic circuit breakers
A
Fuses
A
16 (15)
10 (10)
1.5 (AWG 15)
1.5 (AWG 15)
20 (20)
16 (15)
2.5 (AWG 13)
2.5 (AWG 13)
25 (-)
20 (20)
4 (AWG 11)
4 (AWG 11)
40 (40)
32 (30)
6 (AWG 9)
6 (AWG 9)
63(-)
50 (50)
10 (AWG 7)
10 (AWG 7)
80
63
16 (AWG 5)
16 (AWG 5)
100
80
25 (AWG 3)
16 (AWG 5)
125
100
35 (AWG 2)
25 (AWG 3)
160
125
50
35 (AWG 2)
200 160 70
50
250 200 95
70
300 250 120
95
Table 4.4. – Manufacturer’s recommended minimal conductor section
1. Protection conductor
2. Phase conductor
3. Phase conductor
4. Phase conductor
5. Neutral conductor
6. Molded tube
7. The stripped length of conductors
Figure 4.4.C – Adaptation of conductor ends of supply cable
1. Main switch
2. Turnbuckle
3. -
4. Sag of inlet cable
Figure 4.4.D – Connection of main power inlet