ID Function
Unit, resolu-
tion
Command
33 Set temperature T
set
in Safe Mode (Safe set point in case of communication
interruption).
[°C]
IN_SP_07
158 Actuating signal of master controller in case of external control
[°C]
IN_PV_11
Table 6: Pump
ID Function
Unit
Command
6 Outflow pressure / pump pressure, relative to the atmosphere
[bar]
IN_PV_02
12 Through-flow of the pump
(MID flow controller must be connected)
[l/min]
IN_PV_07
18 Pump power stage
[–]
IN_SP_01
31 Outflow pressure set point / pump pressure (for pressure control settings)
[bar]
IN_SP_06
37 Through-flow control set point
[l/min]
IN_SP_09
71 Status of through-flow control: 0 = off / 1 = on
[–]
IN_MODE_05
154 Outflow pressure of flow controller, relative to the atmosphere
(MID flow controller must be connected)
[bar]
IN_PV_09
156 Pressure limitation set point with active through-flow control
(MID flow controller must be connected)
[bar]
IN_SP_10
157 Overpressure turn off point with active through-flow control
(MID flow controller must be connected)
[bar]
IN_SP_11
160 Valve position of the flow controller
(MID flow controller must be connected)
[%]
IN_PV_12
Table 7: Fill level
ID Function
Unit
Command
9 Bath level (fill level)
[–]
IN_PV_05
Table 8: Actuating signal
ID Function
Unit, resolu-
tion
Command
11 Resolution of controller actuating signal in per mill
– negative value
à
device is cooling
– positive value
à
device is heating
[
‰
]
IN_PV_06
13 Controller actuating signal in watts
– negative value
à
device is cooling
– positive value
à
device is heating
[W]
IN_PV_08