
Numerical values are provided in fixed point format; numbers with up to
4 places in front of the decimal point and up to 2 places after the decimal
point are permitted:
Table 4: Acceptable data formats
-XXXX.XX
-XXXX.X
-XXXX.
-XXXX
XXXX.XX
XXXX.X
XXXX.
XXXX
-XXX.XX
-XXX.X
-XXX.
-XXX
XXX.XX
XXX.X
XXX.
XXX
-XX.XX
-XX.X
-XX.
-XX
XX.XX
XX.X
XX.
XX
-X.XX
-X.X
-X.
-X
X.XX
X.X
X.
X
-.XX
-.X
.XX
.X
Error messages are output with the syntax "ERR_X":
ERR = Identification as an error message
X = Error number (whole number without leading zero, maximum of
4 digits)
Space " " and underscore "_" can be used synonymously.
The interface operates with 1 stop bit, 8 data bits and no parity bits.
4 transmission speeds are available for selection: 2400, 4800, 9600 or
19200 baud. 9600 baud is the factory preset.
Commands from an external source must always end with CR, CRLF or
LFCR. The response from the constant temperature equipment always
ends with CRLF. Meaning of the abbreviations:
CR = Carriage Return, (Hex: 0D)
LF = Line Feed, (Hex: 0A)
In order to ensure that a request and response are uniquely assigned
to one another, commands can only be sent to the constant tem-
perature equipment once a response to the previous command has been
received.
Example with set point transfer of 30.5 °C to the constant temperature
equipment.
PC / control station
Constant temperature equipment
"OUT_SP_00_30.5"CRLF
è
ç
"OK"CRLF
Example
The interface operates with 1 stop bit, 8 data bits and no parity bits.
4 transmission speeds are available for selection: 2400, 4800, 9600 or
19200 baud. 9600 baud is the factory preset.
RS 485 commands are always preceded by the device address; up
to 128 device addresses are available. Device addresses always contain
three digits and start with "A": "A000_..." – "A127_...".
Commands from an external source must always end with CR. The
response from the constant temperature equipment always ends with
CR.
RS 232 protocol
RS 485 protocol
V1
Interface module LRZ 926
19 / 43