2.0  INSTALLATION 

*Note: Each phase converter comes standard with spare fuses for the ones already installed in the

unit. 

2.1  PHYSICAL INSTALLATION 

All  Larson  Electronics  rotary  phase  converter  units  come  standard  in  NEMA  1  indoor  rated 

enclosures. NEMA Type 3R rainproof enclosures are available with the AI series converters.

2.1.1  PHYSICAL INSTALLATION ENVIRONMENTAL CONSIDERATIONS 

The unit should be installed in a location free from the following: 

  Dirt  

  Corrosive gases or liquids 

  Excessive vibration 

  Airborne particles (particularly metal particles) 

  Ambient temperatures exceeding 50 degrees C 

 

High humidity

 

2.1.2  INSTALLATION GUIDELINES (CONTROL PANEL & IDLER) 

Steps to install the control panel and idler: 

a. Mount enclosure on a secure wall or on the idler (idler mount

models only.)  Attach conduit fittings for single phase input line, 3-

phase line to idler and 3-phase line to load.

b. Pull electrical lines into the enclosure.  Be sure to pull enough wire

for your load to reach the two terminals on the left side (L1 & L2)

plus the terminal on the right side (T3) of the phase converter

controls. Run the ground lines with each circuit.

c. Connect the lines to the idler/generator to the terminals marked A,

B and C.

d. Connect the three phase output lines to the terminals marked

L1/T1, L2/T2, and T3.

e. Connect the single phase input lines to the terminals marked L1

and L2.

Summary of Contents for 240 VOLT SERIES

Page 1: ...ALL PURPOSE CNC HEAVY DUTY Rotary Phase Converters 240 480 VOLT SERIES Smart Digital Phase Converter Operation Installation Manual MTPC DRB 208 240 1P 20HP 3P...

Page 2: ...ether and insulated 4 7 5 8 6 9 Do not use wire nuts or ground any of these connections Use the supplied bolts and make all connections insulated Make sure the Phase Converter Panel the Idler Motor an...

Page 3: ...different voltage is needed then a transformer installed in front of the phase converter will be necessary The three phase output is delta configured This means that voltage measurements between phase...

Page 4: ...g 50 degrees C High humidity 2 1 2 INSTALLATION GUIDELINES CONTROL PANEL IDLER Steps to install the control panel and idler a Mount enclosure on a secure wall or on the idler idler mount models only A...

Page 5: ...losure cover is used for clarity f Wire the idler 240V Bolt idler leads 4 5 6 together Insulate this connection with electrical tape or heat shrink tubing Connect the ground line to the ground screw i...

Page 6: ...otect all wire and machinery with proper size breakers Always make sure rotary phase converter starts before external load s are applied A qualified electrician should do all wiring DO NOT assume that...

Page 7: ...minimum recommended based on largest hard starting CNC amps For combined HP s greater than 50 of maximum total HP listed in the tables above consult NEC local codes for conductor sizing The above cha...

Page 8: ...ner by turning the switch to the stop position As with most electrical equipment frequent stops and starts are harder on the rotary phase converter than steady operation The rotary phase converter is...

Page 9: ...tically start loads after the converter reaches full speed 3 3 1 MAINTENANCE Keep dust and moisture from the control panel and the idler Keep dust from accumulating in the motor Dust can be blown out...

Reviews: