H 71 0200 0215 f en - ZMQ202 / ZFQ202 - User Manual
48/88
Installation / De-installation
4.4.1 Check
Procedure
1. Check
the
operating display is
shown. A flashing
'FF' shows fatal
errors.
Operating display
2.
Check phases L1,
L2, and L3 are
present and in the
correct phase
sequence, i.e. L1-
L2-L3.
Phase check
If one phase is not present or the voltage is < 45% Un, the relevant
symbol is absent. With the normal phase sequence the symbols are
displayed continuously.
If the meter is connected with reversed phase sequence (e.g. L2-L1-
L3) the symbols flash.
3.
The energy flow
arrows indicate
whether energy is
being imported (+)
or exported (-).
P = active energy,
Q = reactive
energy.
Energy flow
indicator
4.
All segments of the
display are
illuminated
Display check
5.
R
Enter service menu
Set mode
6.
Select menu item
Installation
diagnostic
7.
Enter installation
diagnostic list
8.
Check the phase
voltages:
Voltage L1:
Code 32.7
Voltage L2:
Code 52.7
Voltage L3:
Code 72.7
Check the phase
currents:
Current L1:
Code 31.7
Current L2:
Code 51.7
Current L3:
Code 71.7
Summary of Contents for ZMQ202
Page 4: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 4 88...
Page 28: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 28 88 Description of Unit...
Page 54: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 54 88 Installation De installation...
Page 66: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 66 88 Operation...
Page 74: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 74 88 Service...
Page 84: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 84 88 Maintenance...
Page 86: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 86 88 Disposal...