Installation/Uninstallation
23/52
D000030875 en q
– E350 series 2, 1-phase ZCF100Ax/Cx – User Manual
© Gyr
4.5
Disconnecting the Meter
Remove main fuses before disconnecting
The connecting wires at the place of installation must not be live when
removing the meter. Touching live parts is dangerous to life. The
corresponding main fuses should be removed and kept in a safe place until
work is completed, so that they cannot be replaced by anyone unnoticed.
For ZxF100xB:
Do not use the disconnector as a main switch for
disconnecting purposes!
The meter remains connected to the mains!
Remove the meter from the network as follows:
1.
Switch off the voltage. The display goes off.
2.
Remove the seal at the terminal cover.
3.
Release and remove the terminal cover.
4.
Ensure with a phase checker that the connecting wire has no voltage.
If there is voltage, remove the main fuse.
5.
Remove the connecting wires of the AMR Module, if available.
6.
Loosen the terminal screws of the phase and neutral connecting wire
with a suitable screwdriver and withdraw the wires from the terminals.
7.
Fit a substitute meter as described in section 4.2 "Connecting the
Meter" and the following sections, if necessary.