Service
45/52
D000030875 en q
– E350 series 2, 1-phase ZCF100Ax/Cx – User Manual
© Gyr
Byte
Bit
Valency
Error code
Error code description
-
3
-
0
1
-
–
-
Not used
-
1
2
-
00 02 00 00
-
Error accessing EEPROM
-
2
4
-
–
-
Not used
-
3
8
-
00 08 00 00
-
Reserved
-
4
1
-
–
-
Not used
-
5
2
-
00 20 00 00
-
Reserved
-
6
4
-
00 40 00 00
-
Error restoring energy registers
-
7
8
-
00 80 00 00
-
Error saving energy registers
-
4
-
0
1
-
–
-
Not used
-
1
2
-
–
-
Not used
-
2
4
-
–
-
Not used
-
3
8
-
–
-
Not used
-
4
-
1
-
–
-
Not used
-
5
-
2
-
–
-
Not used
-
6
-
4
-
–
-
Not used
-
7
-
8
-
80 00 00 00
-
Reserved
* These errors cannot be cleared using the formatted write command
C150 or by power cycling the meter. Contact a Gyr Service
Centre for support.
6.3
Repairing Meters
The following procedure should be adopted if a meter repair is necessary:
1.
If installed, remove the meter (see section 4.5) and fit a substitute meter.
2.
Describe the error found as exactly as possible and state the name
and telephone number of the person responsible in case of inquiries.
Please also state serial no. and complete type designation no.
3.
Pack the meter to ensure it is not damaged during transport. Use the
original packing, if available. Do not enclose any loose components.
4.
Send the meter to an authorised service centre.