Data Sheet
AC01B.C13
Page 4/5
landiaworld.com
Prepared by: BNV
/
GB
Approved by: KSK/TM
Issued on: 1 January 2018
Rev. date:
3
January
201
9
Motor type
3-phase AC motor
Nominal voltage
400 V
Minimum voltage allowed
360 V
Nominal frequency
50 Hz
Applicable for VFD operation
Yes
Ingress protection rating
IP 68
Insulation class
F
ATEX classification
Not possible
ELECTRICAL DATA
Model
Item number
Nominal power
Motor
Full load current
(400 V)
Connection
method
Start current
(DOL)
cos phi
Efficiency
[kW]
[rpm]
[A]
Y/∆
[A]
[%]
PODR-I 3.0 kW-1,500 rpm
1214203
3.0
1,430
6.7
Δ
43
0.79
82.4
PODR-I 4.0 kW-1,500 rpm
1214204
4.0
1,435
8.8
Δ
61
0.78
84.1
PODR-I 7.5 kW-1,500 rpm
1214207
7.5
1,455
15.0
Δ
90
0.83
86.2
PODR-I 11.0 kW-1,500 rpm
1214211
11.0
1,455
21.5
Δ
146
0.84
87.9
PODR-I 15.0 kW-1,500 rpm
1214215
15.0
1,465
29.0
Δ
212
0.84
88.7
PODR-I 18.5 kW-1,500 rpm
1214218
18.5
1,460
35.0
Δ
238
0.85
89.3
For voltages others than 400 V/50 Hz please refer to the attached Appendix.