background image

6

Dispenser Setup

1. 

Purge water to fill carbonator tank by opening carbonator 

relief valve. Close relief valve once water comes out.

A. Relief Valve (Open)

B. CO

2

 Inlet

C. CO

2

 Line

A

B

C

2. 

Activate each valve until a steady flow of water is achieved.

3. 

Turn power off.

4.  Unplug the Pump Motor Connector from the control box. Use 

the wiring diagram either on the unit control box or in the 

back of this manual for reference. 

 

Pump Motor will run for a few seconds to fill carbonator 

tank

NOTE

 

Failure to disconnect the motor power supply will 

damage the carbonator motor, the pump and void the 

warranty.

ATTENTION

5.  Turn on CO

2

 at the source then, using a screwdriver, adjust 

the high pressure regulator at the source to 110 psi (0.758 

MPa) then tighten locknut with wrench.  

6.  Adjust both of the low pressure regulators on the regulator 

manifold to 75 psi (0.517 MPa) then tighten locknut with 

wrench. 

7. 

Activate each valve until gas-out is achieved. 

8.  Plug the Pump Motor Connector back into the control box.

A. Regulator Adjustment Screw

B. Adjust to 75 psi (0.517 MPa)

C. Wrench

A

B

C

9.  Turn power on. 
10. 

Activate each valve until a steady flow of carbonated water is 

achieved. 

Adjust Water Flow Rate & Syrup/Water Ratio

1. 

Close syrup shut-off at mounting block for first valve. 

2. 

Using a Lancer brix cup verify water flow rate (5 oz. in 4 

sec.). Use a screwdriver to adjust if needed.

A

B

A. Plain Water ON     

B. Syrup Closed

6.  Using a wrench, loosen lock nut on the regulator adjustment 

screw of the high pressure CO

2

 regulator connected to the 

source, then using a screwdriver back out lock nut screw all 

the way.

 

DO NOT TURN ON CO

2

 SUPPLY AT THIS TIME

WARNING

A. CO

2

 Regulator

B. Screwdriver

C. Loosened Lock Nut

D. Regulator Adjustment Screw

A

B

C

D

7.  Repeat Step 6 for both low pressure CO

2

 regulators on the 

regulator manifold routed to the unit and the syrup pumps.  

A

B

Increase

Decrease

C

A. Flow Control, Water

B. Flow Control, Syrup

C. Nozzle (Diffuser inside)

D. Mounting Block (not shown)

E. Soda Lever

D

E

 

Do not set flow rates or dispense from the unit until 

after a complete ice bank is established.

NOTE

Summary of Contents for 9000 series

Page 1: ...sion 00 0 April 2020 The dispenser is for indoor use only This unit is not a toy Children should be supervised not to play with appliance It should not be used by children or infirm persons without su...

Page 2: ...it Do not plug into a wall electrical outlet unless the current shown on the serial number plate agrees with local current available Follow all local electrical codes when making connections Each disp...

Page 3: ...the counter top the dispenser base must be sealed to the counter top with a bead of clear silicone caulk or sealant which provides a smooth and easily cleanable bond to the counter 3 Once the dispens...

Page 4: ...cm could cause the lines to freeze ATTENTION The water bath compartment must be filled with water before plugging in the unit otherwise the compressor fan may not operate properly DO NOT use RO or pu...

Page 5: ...is present in regulator attachment nut ATTENTION Installing CO2 Supply 1 Connect high pressure CO2 regulator assembly to CO2 cylinder or bulk system Thread regulator nut on to tank then tighten nut wi...

Page 6: ...Plug the Pump Motor Connector back into the control box A Regulator Adjustment Screw B Adjust to 75 psi 0 517 MPa C Wrench A B C 9 Turn power on 10 Activate each valve until a steady flow of carbonate...

Page 7: ...of the first valve 2 Insert the programmer s 10 pin connector into the ID panel plug located on the front of the circuit board 3 When properly connected the programmer will run a self diagnostic test...

Page 8: ...amination DO NOT use strong bleaches or detergents These can discolor and corrode various materials DO NOT use metal scrapers sharp objects steel wool scouring pads abrasives or solvents on the dispen...

Page 9: ...t until there is no aftertaste Do not use a fresh water rinse This is a NSF requirement Residual sanitizing solution left in the system creates a health hazard CAUTION Cleaning and Sanitizing Nozzles...

Page 10: ...yrup flow control 5 Bad syrup pump 1 Adjust CO2 pressure to 80 psi 0 550 MPa minimum 70 psi 0 480 MPa for BIB pumps 2 Replace CO2 tank refill 3 Open shutoff fully 4 Remove syrup flow control form uppe...

Page 11: ...3 Water flow rate too high 4 Nozzle and diffuser not installed 5 Nozzle and diffuser not clean 6 Air in BIB lines 7 Poor quality ice 8 High beverage temperature 1 Correct prior to dispenser Consider...

Page 12: ...ide com lancerworldwide com WIRING PLUMBING DIAGRAMS Plumbing Diagram PLAIN WATER COILS CARB HIGH PRESSURE WATER PUMP V6 V5 V4 V3 V2 V1 S2 S1 S3 S4 S5 S6 PRESSURE SETTINGS CO 75 psi 50 psi WATER 2 PLA...

Reviews: