17
TROUBLE
CAUSE
REMEDY
4.6 Compressor and Condenser Fan
Motor will not start after five (5) minute
Power Off Delay
(Lancer EIBC Export
only)
A. Fuse blown on EIBC PCB.
B. Relay will not turn on compressor
C. Transformer tripped.
D. Probe unplugged
A. Replace fuse on EIBC PCB.
B. Failed relay. Replace Control Board.
C. Reset transformer.
D. Check probe connections at PCB.
4.7 Compressor and Condenser Fan
Motor will not start after five (5) minute
Power Off Delay
(Lancer EIBC, USA
Only)
A. Improper Wiring
B. Probe Unplugged
C. Damaged Electronics
A. Check Power Indicator Lamp; check
wiring per Wiring Diagram.
B. Check Probe connection at PCB.
C. Replace Control
4.8 Warm Drinks
A. Restricted airflow
B. Dispenser connected to hot water
supply.
C. Refrigeration system not running.
D. Refrigeration leak.
E. Condenser fan motor not working.
F. Dirty Condenser.
G. Dispenser capacity exceeded.
A. Check clearances around sides, top,
and inlet of unit. Remove objects blocking
airflow through grill.
B. Switch to cold water supply.
C. Refer to Sections 4.1 - 4.7.
D. Repair and recharge.
E. Replace condenser fan motor.
F. Clean condenser.
G. Add pre-chiller.
4.9 Motor fails to start (Motor hums)
A. Pump binding.
B. Open Winding infield.
A. Loosen Pump Clamp and rotate Pump
slightly to free binding, if this fails, replace
pump.
B. Replace Motor.
4.10 Motor fails to start (Motor does not
hum)
A. Cutout due to overloading by pump
binding.
B. Blown Fuse, or Circuit Breaker tripped.
C. Defective Motor.
D. Defective PC Board.
E. Defective Probe.
A. Let Motor cool and follow Pump
binding remedy.
B. Replace Fuse or reset Circuit Breaker.
C. Replace Motor.
D. Replace PC Board.
E. Replace Probe.