68
8
Options
8.5.2
LEDs
PBM100 has 4 LEDs which are connected as described below:
8.5.3
PROFIBUS DP Communication
Specification of the PB master input data
In the following, the input data that the PBM transfers to the master is specified:
LED
Colour
Description
PWR
green
ON:
Module working in normal mode = fully initialised and
without any fault.
CAN
green
OFF:
No communication or CAN BUS error
Blinking with 2 Hz:
Errors (optional, if a CAN warning is
detectable)
ON:
CAN is ready.
PB
green
OFF:
no communication via PROFIBUS DP
ON:
communication without error via PROFIBUS DP
ERR
red
OFF:
no errors
ON:
PBM100 Initialisation incomplete or not yet success-
fully completed or CAN message missing for more than 3 s.
Byte position
*
*
Byte-number-wise from 1
Designation
Configuration
1, 2
CO
e
actual value
CO
e
display value,
uint 16 value in ppm
3, 4
CO
e
actual value status
Measure value status (CO/O
2
)
and edge information (see the Bit encoding
CO/O2 actual value status in Chapter
5, 6
O
2
actual value
O
2
display value,
uint16 value in [ppm], for status, see CO
e
7, 8
CO sensor voltage raw
Electrode voltage 1,
int16 value in [1mV]
9, 10
O
2
sensor voltage raw
Electrode voltage 2,
int16 value in [1mV]
11, 12
Probe voltage U
COe
Effective CO voltage,
int16 in [0.1mV]
13, 14
LT3 status
Device status bit-encoded
15, 16
Warning word 1
LT warnings bit-encoded,
Bit [0 ... 15] for each warning 1 ... 16
17, 18
Warning word 2
LT warnings bit-encoded,
Bit [16 ... 31] for each warning 17 ... 32
19, 20
Fault word 1
LT faults bit-encoded,
Bit [0 ... 15] for each warning 1 ... 16
21, 22
Fault word 2
LT faults bit-encoded,
Bit [16 ... 31] for each warning 17 ... 32
Summary of Contents for LT3
Page 2: ......
Page 14: ...13 3 Product Description 3 2 C Declaration of Conformity...
Page 15: ...14 3 Product Description...
Page 19: ...18 4 Display and Operational Controls 4 2 4 Settings Menu Structure...
Page 22: ...21 4 Display and Operational Controls 4 4 1 Main Menu Password Entry...
Page 79: ...78 11 Appendix...