69
8
Options
Specification of the PROFIBUS master output data
The following shows the assignment of the output data received by the PBM from the PROFI-
BUS master.
NOTICE
If the PROFIBUS module is used with a BT300 with software version 3.3 or older, only select-
ed LSB digital modules can be used (see the LSB module ID table in Chapter
8.5.4
Communication Appendix
Bit encoding status of the digital outputs of the LSB module
ID of LSB modules – address to be set on the rotary switches
Byte position
*
*
Byte-number-wise from 1
Designation/configuration
1, 2
Fault/warning reset
Execution for change byte 1, 2 of 0x55AA
0xAA55
0xAA55
0x55AA
3
ID (number) of digital module 1 ...16
**
** Here, specify the number of the digital module (1 ... 16), and
set the address on the LSB module according to the number and LSB family; cf.
4
Bit encoding of the digital outputs to be set
Bit [0 ... 3]
digital outputs 1 ... 4 (see the Bit encoding status of the digital
outputs of the LSB module table in Chapter
.
Digital outputs
Active (bit encoding)
1
0x01
2
0x02
3
0x04
4
0x08
LSB module no.
LSB family
1
2
3
4
BT300 support
Until Release 3.3
Digital module 1
3
2
1
0
Digital module 2
7
6
5
4
Digital module 3
11
10
9
8
Digital module 4
15
14
13
12
Digital module 5
18
18
17
16
Digital module 6
23
22
21
20
Digital module 7
27
26
25
24
Summary of Contents for LT3