71
8
Options
8.5.5
External Connection
NOTICE
It is prohibited to use the terminals!
Recommendation for line lengths and line cross-sections of the LAMTEC SYSTEM
BUS:
•
0 - 40
m
2
x
2
x
0.34
mm
2
, cabled in pairs with screening, impedance 120
•
40 - 300
m
2
x
2
x
0.5
mm
2
, cabled in pairs with screening, impedance 120
•
300 - 500
m
2
x
2
x
0.75
mm
2
, cabled in pairs with screening, impedance 120
Example cable type for fixed installation:
•
LAPP cable 2170267 (LAMTEC article no.: 05L05 2
x
2
x
0.5).
•
HELU cable 800685.
8.6
LSB Module for Calculating Combustion Efficiency
Setting of LSB address not necessary.
Terminals may not be connected!
1
CAN/LSB
2
DC power supply
(safety extra low voltage)
Terminals may not be connected!