MEASUREMENT 11 SETTING
Directions for entering the
maintenance mode are on page 19.
Erikoishuolto
Aset.palautus
Asetusarvot
Mitt. asetukset
Meas.11 setting
Hot gas
Measure 11
Not connected
Labeling measurement 6 using the text editor:
The factory setting for measurement 6 is
"Hot gas" -measurement.
Relabeling is shown on page 9.
The
character indicates which measurement has been chosen for
measurement 6.
Selecting measurement 11:
Name change
Measure 11
Give new label
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Meas.11 setting
Dig1 selection
The value of measurement 11 can be changed in this special maintenance
mode. ”Hot gas” is a factory setting.
Press the
button to move the cursor to what you want to connect to
measurement 6. Press
OK
.
Press the
button to move the cursor to "Meas. 11 setting". Press
OK
.
Hot gas temperature:
If the hot gas temperature exceeds 125°C the compressor cannot start up.
33