Factory
settings:
Press the
button to move the cursor to ”Settings". Press
OK
.
Explanation:
The average inside temperature measurement time which
the room compensation uses.
Drop in supply water temperature when the exhaust fan is
at ½ speed.
The length of time from which the regulator calculates the
HW average temperature for the alarm.
Lower limit of supply water during a free temperature drop
in the regulating circuits H1/H2 when the outdoor
temperature is 0°C. (stand-by function)
Lower limit of supply water during a free temperature drop
in the regulating circuits H1/H2 when the outdoor
temperature is -20°C. (stand-by function)
H1/H2/HW supply water temperature deviation from the
setting determined by the regulator which causes the
alarm
The alarm goes off if the deviation has lasted for the set
time.
Range:
0...2
5...20
5...20
10...50
10...50
1...75
1...75
1...75
0...90
0...-10
0...120
INFORMATION ABOUT SPECIAL MAINTENANCE SETTINGS:
Directions for entering the
maintenance mode are on page 19.
0.5h
10°C
10°C
30°C
30°C
75°C
75°C
75°C
60 min
-6°C
30s
Settings:
Attention!
SETTINGS
Settings
H1SuppMin(0)
H1SupMin(-20)
H2SuppMin(0)
H2SupMin(-20)
H1 Dev.alarm
DevAlaDela
min
1/2exhst
°C
HW AlarmDel
s
Room delay
h
H2 Dev.alarm
HW Dev.alarm
0.5
10
30
10
30
-6
30
75
60
75
75
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Room delay
H1 SuppMin (0°C)
H2 SuppMin (0°C)
H1 SupMin(-20°C)
H2 SupMin(-20°C)
½ exhst
HW AlarmDel
H1 Dev. alarm
H2 Dev. alarm
HW Dev. alarm
DevAlaDela
In the 203GT heating regulator the user can adjust most of the
settings (see settings p. 6-8). Some of the settings that control the
regulator's functions can be set in the maintenance mode (see page 21)
and some in special maintenance. Seldom needed settings can be
adjusted in special maintenance.
Press the
button to move the cursor to the parameter that you want
to change. Press
Press the
or
button to change the setting. Press
OK
OK
.
.
-
+
Only H1
30