RAGGIO C
193
EN
cod. 3541V280 - Rev. 01 - 04/2021
Notes:
1. Parameters with more than one description vary their function and/or range in relation to the
setting of the parameter given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given
in brackets is modified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
To return to the service menu, simply touch the "arrow" icon
in the top left corner of the screen.
Combustion Control Menu
ONLY QUALIFIED PERSONNEL CAN ACCESS THE MENU AND MODIFY THE RELEVANT
PARAMETERS.
P46
DHW user max. set-
point
40 ÷ 70°C
55°C
P47
DHW pump Post-Cir-
culation
0 ÷ 255 seconds
30
P48
Max. output in DHW
0 ÷ 100%
RAGGIO 28 C
= 100%
RAGGIO 34 C
= 100%
P49
Not implemented
--
--
P50
Not implemented
--
--
P51
Solar off temperature 0 ÷ 100°C
10°C
P52
Solar on temperature 0 ÷ 100°C
10°C
P53
Solar standby time
0 ÷ 255 seconds
10
P54
Heating deltaT adjust-
ment temperature
0 ÷ 60°C
18°C
P55
Primary exchanger
protection temperature
0 ÷ 150°C
43°C
P56
System min. pressure
value
0 ÷ 8bar/10
4 bar/10
P57
System nominal pres-
sure value
5 ÷ 20bar/10
7 bar/10
P58
Exchanger protection
intervention (b01=3)
0
= No F43
1 ÷ 15
= 1 ÷ 15°C/second
10°C/second
P59
Heating hysteresis
after ignition
6 ÷ 30°C
10°C
P60
Timer for heating hys-
teresis after ignition
60 ÷ 180 seconds
60
P61
Pump deactivation
with OpenTherm
0 ÷ 1
0
P62
System filling mode
Manual
Automatic
Manual
Code
Description
Functional description
Range
Default
Sc01
Gas type selection
Allows the change of gas type. See “Gas
conversion” on page 186
NG/LPG
NG
Sc02
Ignition gas setting
Allows the amount of gas to be increased or
decreased in the ignition phase in case of
difficult starting.
-9 ÷ 20
0
Sc03
Ignition power
Allows the fan speed to be increased or
decreased in the ignition phase in case of
difficult starting.
-16 ÷ 14
0
Code
Description
Range
Default