RAGGIO C
190
EN
cod. 3541V280 - Rev. 01 - 04/2021
• Press
[Test Mode]
.
• Touch the buttons
[+]
or
[-]
to increase or decrease the power (from 00 = minimum to 100 =
maximum)
The set power is stored instantly.
Press
[
]
to return to the
[
Service Menu]
or
[
]
to return to the main screen.
System diagnostics
The values of the sensors and actuators in the boiler are available.
Note:
To return to the
Service Menu
, touch the arrow at the top left of the screen
Menu [Transparent parameters B]
A
By selecting a parameter on the screen, the possible values will be shown. If the values
shown do not match those indicated in the corresponding "Range" column, check that the
parameter
B01
is correctly set to
RRT
.
Description
Range
Combustion
Burner power
00% = Minimum
100% = Maximum
Flame status
00 ÷ 255
Fan rpm
00 ÷ 12000
Operating hours
00 ÷ 99999
Fume Temperature
0 ÷ 125 °C
Hydraulics
Heating Flow
0 ÷ 125 °C
Heating Return
0 ÷ 125 °C
NTC DHW sensor (°C)
0 ÷ 125 °C
DHW draw-off
0.0 ÷ 99.9 L/min
Modulating pump speed
00 ÷ 100%
System water pressure
00 ÷ 9.9 bar with pressure transducer
Environment
External probe
-30 ÷ +70°C
Code Description
Range
Default
B01
Boiler type selection
RRP
(INSTANTANEOUS COMBI)
RRH
(HEATING ONLY also with OPTIONAL HOT WATER
STORAGE TANK
RRT
(COMBI HEATING ONLY)
RRK
(HEATING ONLY with HOT WATER STORAGE
TANK)
RRT
B02
Exchanger type
1 ÷ 4
RAGGIO 28 C
=
2
RAGGIO 34 C
=
3
B03
Absolute Maximum Heat-
ing Power
0 ÷ 100%
(Do not modify the value)
RAGGIO 28 C
= 85%
RAGGIO 34 C
= 85%
B04
System water pressure
protection selection
Pressure switch
Pressure Transducer
Pressure transducer
B05
NOT IMPLEMENTED
--