DESCRIPTION
BANOX 24 PLUS MB W TOP - BANOX 28 PLUS MB W TOP
Perfectly air-tight with respect to its surroundings, this unit is suitable for heating water to temperatures below
boiling point at atmospheric pressure. Fully automatic, the BANOX PLUS boiler is governed by an electronic
microprocessor-operated control box.
Continuous power modulation is effected both on the heating circuit and the hot water circuit, by means of an
electronic board controlling fan r.p.m.
Combustion analysis (indispensable at the first ignition) allows adjustment of gas delivery flow-rate so that the
right air/gas mix is always obtained. Each variation in fan r.p.m. (and the resulting air-flow) corresponds to a
variation in the gas delivery rate.
This operation ensures a constant air-gas ratio whatever the flame intensity, thus guaranteeing maximum
combustion efficiency and hygiene under all working conditions.
The electronic board also provides:
-
3-way valve and circulation pump efficiency test; this prevents the lock-out that might otherwise occur
when the boiler remains idle for a prolonged period (the valve and pump are operated for a set time every
24 hours).
-
Anti-freeze device:
when the heating water temperature falls below 10
°
C the circulation pump comes
on. If temperature continues to fall the burner will ignite at 3
°
C, burning at
minimum. It will be switched off when the water is reheated to 10
°
C.
This is why
the boiler must be left connected to the power supply even when it is not in
use.
-
Board memory:
The control box microprocessor will memorise and signal any anomalies. This
information is stored on the memory even when the power is off and can be
recalled by connecting up to a PC.
-
Possibility of connecting up with an external temperature sensor: the external sensor (optional) allows
automatic variation of the boiler water delivery temperature as a function of outdoor temperature.
73
de 10 a 60 (centenas)
Revoluciones/min. máx. en calefacción
F
00 = modulación activa.
De 01 a 100% control manual de la
velocidad del ventilador.
Control velocidad ventilador
E
d
0x = termostato ambiente
1x = sonda NTC4 (sonda externa)
Tipo caldera
1
a
cifra tipo Calefacción
2
a
cifra tipo A.C.S.
x0 = válvula de 3 vías
x1 = bomba A.C.S. -
No utilizar
x2 = válvula de 3 vías invertida -
No
utilizar
C
No utilizar
Bomba PWM
Tiempo de espera para volver a encender la
calefacción
De 0 a 30 (x 10.2 segundos)
b
Tiempo de postcirculación. Bomba en
calefacción
De 3 a 99 minutos
A
De 15
°
C a 30
°
C
Desplazamiento paralelo (con sonda
externa y reloj en la caldera)
Temperatura de espera para volver a
encender la calefacción
De 0
°
C a 30
°
C (en T1
set
)
De 5
°
C a 15
°
C
Histéresis Calefacción central
7
8
9
Sistema calefacción central
00 = Calefacción central apagada
01 = Calefacción central encendida
02 = Calefacción central enc bom-
ba continua
Temperatura de ida (T1)
De 20
°
C a 90
°
C (mínimo preestablecido
55
°
C)
T1
foot
(temperatura mínima de calefacción)
De 15
°
C a 25
°
C (se aconseja 15
°
C)
T4 mínimo (temperatura que se puede
establecer para la sonda externa)
De -20
°
C a +10
°
C
3
4
5
6
Después de haber programado hay que
presionar
Campo de valores
Parámetro
N
o
fase