10. Appendices
10.1. Factory settings for idOil Solar
Every idOil Solar alarm unit has the following settings pre-defined in the factory.
The
Low power settings
of idOil Solar can be changed from idOil-30 Control Unit's
settings either through the web user interface or by text messages:
Beacon light adjustment:
Repeat time (factory setting 10 s)
Duration (factory setting 600 ms)
Beacon connected to relay 1 or relay 2 (factory setting off)
Measuring interval:
Repeat (factory setting 10 min)
Start delay (factory setting 5 s)
Display Backlight blinking during alarm (factory setting ON)
Battery voltage monitoring:
current battery voltage level
Monitoring (factory setting ON)
Battery low voltage alarm (factory setting 11,4 V)
Most of the factory settings can also be set by text messages.
Command
and
parameters
Explanation
DI 1:
1: Oil level sensor.
2: High liguid sensor.
3: Sludge level sensor.
Command sets probe names as follows:
Probe nbr 1 is identified as “Oil level sensor”.
Probe nbr 2 is identified as “High liquid sensor”.
Probe nbr 3 is identified as “Sludge level sensor” .
VLIM 11.4
Alarm level (in Volts) for minimum battery voltage.
MI 10
Measuring interval
idOil Solar wakes up every 10 minutes for 20 seconds from
low-power mode to check the status of probes.
LI 12
Listening interval (hours)
idOil Solar wakes up from normal (low-power) mode every 12
hours (starting from the time idOil is put to low-power mode)
for 2 minutes to check if users have given new SMS
commands, and to answer them.
More information about the format of each command and parameter can be found from the
following documents:
idOil-30 Battery, Installation and Operating Instructions (DOC001699).
idOil-30 Battery 3G, SMS-messages - Commissioning and use (DOC001696).
Installation and Operating Instructions | idOil Solar
55/58
DOC001599-EN-3