3.3.5. idOil-LIQ High Liquid Level Sensor
The idOil-LIQ sensor is installed above the separator outlet’s
upper level. It monitors the total level of the separator,
regardless of the existence of the oil layer or sludge in the
separator.
The sensor can be mounted suspended from the ceiling of the
separator by the cable. Please check the correct installation
depth from the oil separator instructions.
The principle of measurement is ultrasonic. The sensor is
normally mounted in the air.
idOIL-LIQ sensor can be installed in a zone 0, 1 or 2 potentially explosive atmosphere.
3.3.6. Flashing Beacon
The idOil Solar can be equipped with a flashing beacon for
visual alarms. In case of alarm, a highly visible signal
flashes once every 10 seconds.
The beacon is mounted on the top of the idOil Solar enclosure.
The beacon is IP67 rated.
In case of an alarm, the idOil Solar can operate the flashing the beacon for about 10 days
with no sun-light, before the battery becomes discharged. In practise, there is always some
solar power available, so the idOil Solar may function much longer with no interruption.
3.3.7. Main Power Switch
The main power switch is located inside of the idOil Solar enclosure (see figure
System
components)
. Main switch connects and disconnects both battery terminals and the solar
panel of the system.
The main power switch must be in
ON
position during normal low-power operation. The
switch is in
OFF
position during delivery.
Installation and Operating Instructions | idOil Solar
11/58
DOC001599-EN-3