background image

46

• 

You are prompted to repeat the new password, so enter again the previous combination.

• 

If  the  password  entered  is  correct,  the  message  “PASSWORD  OK”  is  displayed  for  one 

second, then the system returns to the PASSWORD MANAGEMENT section. Press the EXIT 

 button to return to the general programming menu

• 

If the password you entered does not match the previous one, the display shows PASSWORD 

ERROR, the system returns to the section PASSWORD MANAGEMENT and it is necessary to 

perform again the procedure.

• 

Enter the primary password 

• 

Enter the new service password, selecting a combination of 5 characters from the letters A-B-

C-D.

• 

You are prompted to repeat the new password, so enter again the previous combination.

• 

If  the  password  entered  is  correct,  “PASSWORD  OK”  is  displayed  for  one  second  and  the 

system returns to the PASSWORD MANAGEMENT section.

21.3) HOW TO CHANGE THE SERVICE PASSWORD

• 

Select “SERVICE PASSWORD”

• 

Press OK (F1).

Press the EXIT 

 

 button to return to the general programming menu.

If the password you entered does not match the previous one, the display shows PASSWORD ERROR, the system returns to the section 

PASSWORD MANAGEMENT, and it is necessary to perform again the procedure.

Summary of Contents for NEPTIS PLUS

Page 1: ...lation Manual ENG Rel 1 0 04 2021 CD0450EN NEPTIS PLUS Automation for pedestrian automatic swing door EN English TRANSLATION OF THE ORIGINAL INSTRUCTIONS NB SLT NB SLTB NB LET NB LETB NB SMT NB SMTB I...

Page 2: ...6 7 EXTENSION FOR EXTB Z TAPERED PIN 16 7 PREPARATION AND INSTALLATION OF THE AUTOMATION 17 7 1 TOOLS REQUIRED 17 7 2 AUTOMATION CHECK 17 7 3 AUTOMATION INSTALLATION 18 7 4 CHOICE OF THE SPRING LOAD...

Page 3: ...RIC LOCK ELECTRIC STRIKE 53 25 2 ELECTROMAGNET 53 26 DUAL LEAF DOOR 54 26 1 DUAL LEAF ELECTRIC SETUP 54 26 2 DUAL LEAF DOOR COMMISSIONING 54 26 3 FUNCTIONAL TESTING 57 26 4 PARTIAL OPENING 57 26 5 CON...

Page 4: ...be installed in explosive environments or atmospheres or in the presence of flammable gases or fumes Make sure that the characteristics of the electric distribution network are compatible with the tec...

Page 5: ...emergency battery is required The automation must be installed in indoor environments All models are reversible so in case of power failure it is possible to open the door manually Before starting ins...

Page 6: ...SHLESS GEARMOTOR 6 MOTION TRANSMISSION SHAFT OUTLET 7 INTERNAL WIRING BETWEEN LCB AND PWB CARDS 8 SPRING PRELOAD LOCKING SCREW 9 PLASTIC PLATE 10 SWITCHING POWER SUPPLY 11 NB BAT MODULE BATTERY CHARGE...

Page 7: ...out the run The door requires mechanical stops consisting of a mechanical stop in open position and a final stop in closed position The mechanical opening stop is not supplied with the automation In c...

Page 8: ...ease consider that the gearmotor must be on the hinged side of the door for a correct opening movement direction 5 1 ASSEMBLY OF THE AUTOMATION ON THE TRANSOM FROM THE HINGE SIDE SLIDE PULL ARM BDT2 F...

Page 9: ...nsider that the gearmotor must be on the hinged side of the door for a correct opening movement direction Usable leaf length and weight Usable leaf length and weight with different fastening dimension...

Page 10: ...PRING MODELS NB LET LETB SLT SLTB For this application please consider that the gearmotor must be on the hinged side of the door for a correct opening movement direction Automation with battery module...

Page 11: ...oor position A STANDARD TAPERED PIN Should it be necessary to increase the distance between the automation and the arm dimension X replace the standard tapered pin with the following optional extensio...

Page 12: ...n opening It is necessary to install a mechanical stop in open door position A STANDARD TAPERED PIN Should it be necessary to increase the distance between the automation and the arm dimension X repla...

Page 13: ...For this application please consider that the PWB cabling board must be on the hinged side of the door for a correct movement direction when opening It is necessary to install a mechanical stop in ope...

Page 14: ...f The pin 6 shall be inserted into the sliding guide shoe 6 2 SLIDING ELBOW ARM BSG 150 BSG 250 a Insert the M8 x 70 screw 2 in the tapered pin 1 b Insert the long arm rod 4 into the closed shell 3 c...

Page 15: ...the pull arm pin shall operate c Insert the striker 5 into the sliding guide and fasten it at the opening limit position with the dowel d Place the cover casing 2 on the sliding guide 1 e Insert the t...

Page 16: ...tension with the tapered pin and insert the central screw E tighten the two M6 X 65 side screws F insert the extension into the arm and tighten the two M6 X 20 screws G 6 6 EXTB Z TAPERED PIN Use the...

Page 17: ...type and to the automation installation type carefully refer to the technical drawings in paragraph 5 For NB LET NB LETB NB SLT NB SLTB automations only do not remove the spring preload locking screw...

Page 18: ...t with the leaf completely closed to obtain a high re closing force maximum spring load 7 5 INSERTION OF THE ARM TAPERED PIN Make sure that the plastic plate is inserted in the mechanical body of the...

Page 19: ...ocked Removing the tapered pin s setscrew can cause the pulleys and gears of the automation to move if the re closure spring has not been locked in advance Move your fingers or other body part away fr...

Page 20: ...r supply than cut the straps holding it fastened to the mechanical body of the automation b Remove the plastic side caps from the automation by unscrewing the relevant screws c Detach the NB BAT modul...

Page 21: ...see paragraph ELECTRICAL CONNECTIONS d Erase the set up if it has already been stored on the automation control unit see paragraph MAINTENANCE e Press and hold pressed the PS1 START button on the PWB...

Page 22: ...the automation Neptis Plus there are holes that must be broken open through which the electric cables must be inserted The installer must take care to secure the power supply cable inside the automati...

Page 23: ...st be positioned corresponding to the end of the door O A E D G E T L LEFT SENSOR O A E D G E R R RIGHT SENSOR POWER SUPPLY CUT OFF SWITCH EARTH NEUTRAL LIVE MANUAL PROGRAM SELECTOR SECONDARY SENSOR M...

Page 24: ...TART COMMON AUX1 E C COMMON AUX2 E O OPEN COMMON RADAR EX RADAR IN START COMMON ET DSEL DIGITAL PROGRAMMER M6 TEST GND AUX3 24V O C 24V L1 J5 M4 T NFC J1 25 26 27 28 29 8 9 10 11 A B 1 2 3 4 5 6 7 J4...

Page 25: ...operating programs For details refer to the Interlock System paragraph Terminals 28 29 Open Collector NPN output The operation depends on the setting of function F41m see FUNCTION TABLE Connect a max...

Page 26: ...e installer to configure the automatic door operation and perform the setup and function parameter setting operations to carry out the system diagnostics and to access the event memory containing info...

Page 27: ...nsor installed on closing side F11 S05 ON Closing safety sensor F12 S06 ON Opening safety sensor F13 S07 ON TEST of closing safety sensor F14 S08 ON TEST of opening safety sensor F15 S09 OFF Test leve...

Page 28: ...eaf automatic door refer to the paragraph Dual leaf door Follow chapter 16 1 only if the digital selector ET DSEL is new and is powered on for the first time Follow chapter 16 2 if the digital selecto...

Page 29: ...default password See paragraph Password Management 16 3 INITIAL SETUP From the general programming menu the F1 button allows moving forward among menu symbols Select the INITIAL SETUP symbol Press qu...

Page 30: ...he safety sensors The setup depends on the characteristics of the sensor installed If the type of sensors in use is FLAT SCAN or OA EDGET select OFF If the type of sensors in use is TOP SCAN S select...

Page 31: ...n the power limit is reached set the F49 function to ON see Functions setup The buzzer noise for almost the entire run means that the leaf exceeds the limits allowed or that the installation dimension...

Page 32: ...al box of the PWB control unit if the mechanical selector EV MSEL is installed ELECTRIC CONNECTIONS Terminal 1 of EV MSEL to terminal 9 Internal radar of the PWB of the Neptis Plus automation Terminal...

Page 33: ...g Manual free door Automatic operation is disabled and the door can be opened manually Automatic bidirectional program The door automatically opens after an opening command Automatic unidirectional en...

Page 34: ...TENTIOMETER TABLE Press again button F2 in order to activate the virtual spring function The symbol F2 on the display disappears F1 Door opening command Press the button F1 to open the door but only i...

Page 35: ...the selected sub menu press briefly the ENTER button To exit the general programming menu and return to the work program view press the EXIT button DIAGRAM 1 If you enter the initial setup section se...

Page 36: ...of the display it is displayed the letter M button to return to the general programming menu 19 1 FUNCTIONS SETTING In this section the display describes the purpose of the selected function the butto...

Page 37: ...anual program selector in position II selection of the work program night lock ON Operating mode of manual program selector in position II selection of the work program open door F071 OFF Battery modu...

Page 38: ...l and external radar inputs ON Operation with separate opening and closing commands The external radar input controls the opening the internal radar input controls the closing without automatic closin...

Page 39: ...ure during the first opening movement the leaves start respecting the offset F36m Multiple selection function Multiple selection function allowing to set the position of the manual or mechanic program...

Page 40: ...FUNCTION F78 Function enabled if the function F77 ON OFF for electromagnet not equipped with open closed status sensor factory setting The Neptis Plus automation automatically detects the closed door...

Page 41: ...af speed in the last degrees of the closing movement to ease the engagement of the electric lock S P10 Potentiometer enabled if F02 ON Closing thrust to release the electric lock At the default value...

Page 42: ...losing ledge in which the closing movement stop is achieved without reversing the running direction in case of detection of an obstacle S P25 Intensity of door braking at the end of the opening after...

Page 43: ...is automatically released after the door has been locked from the inside If the value is 0 factory setting time is infinite therefore the electromagnet remains locked until the user activates the insi...

Page 44: ...password and to be very careful not to forget it b PRIMARY PASSWORD for the system owner user It is a 5 character password used by the user to prevent unauthorized persons from having access to the se...

Page 45: ...ct PRIMARY PASSWORD Press OK F1 Enter the default primary password A A A A A pressing 5 times the button A If the primary password is not the default password since it had already been changed before...

Page 46: ...rocedure Enter the primary password Enter the new service password selecting a combination of 5 characters from the letters A B C D You are prompted to repeat the new password so enter again the previ...

Page 47: ...to enable password usage it is recommended to change the combination of both primary and service password 21 5 DISABLING USER PASSWORD USAGE From the PASSWORD MANAGEMENT section select PASSWORD ON OFF...

Page 48: ...o use Bidirectional program The buttons in this submenu are used as follows The button allows going to the next function The button F2 allows returning to the previous function The button F1 sets the...

Page 49: ...mation of the Slave automation Each pulse on the button F3 allows switching from M to S and vice versa In case of single leaf automation on the top right of the display it is displayed the letter M Th...

Page 50: ...ation I5 Version of microcontroller B Displays the software release of the microcontroller B of the logic card LCB of the automation I6 Identification number Identification number including data for m...

Page 51: ...ected It is necessary to turn off the 230V power supply then turn it on again after a few seconds Check that the motor is running that the motor connector is properly plugged in and that the motor cab...

Page 52: ...automation on the top right of the display it is displayed the letter M The GENERAL RESET clears the setup 24 1 PLUG AND PLAY The PLUG and PLAY option allows to set the functions and the parameters o...

Page 53: ...st degrees of the closing movement to ease the engagement of the electric lock P10 Power of the closing thrust before door opening to ease electric lock release At value 0 the function is disabled fro...

Page 54: ...e electric lock must be connected to the Master automation The safety sensors installed on the master leaf must be connected to the Master automation the safety sensors installed on the slave leaf mus...

Page 55: ...Enter the 10 character technical password to access setup for information about the use of the technical password refer to the paragraph Password management 21 and 21 1 BEFORE STARTING THE SETUP MOVE...

Page 56: ...to monitor the safety sensors The setup depends on the characteristics of the sensor installed Select OFF when using OA EDGE T or FLAT SCAN sensors Contact configuration on OPEN input between terminal...

Page 57: ...at slow speed and you can choose with the function F35 if both leaves must start together or one after the other respecting the leaf delay F35 OFF In the first opening cycle the leaves start together...

Page 58: ...ay On the top right of the display appears the letter M if the information is related to the Master operation the letter S if it is related to the Slave automation button F3 toggles from Master to Sla...

Page 59: ...The radio control opens the door in all the operating programs of the automation 5 RECEIVER MEMORY ERASURE Should it be necessary to erase all the transmitter codes saved in the memory of the receive...

Page 60: ...of the automation The disabled can also use the SPYCO radio control paired with the radio receiver EN RF1 Set the pause time P05 potentiometer so as to keep the door open for a sufficient time to all...

Page 61: ...TERY CHARGED WITHOUT MAINS VOLTAGE OFF ON WARNING Periodically check battery efficiency To allow recharging the batteries must always be connected to the electronic control unit The equipment must be...

Page 62: ...automatic doors can operate independently To enable interlocked operation you need to install the digital selector ET DSEL or T NFC as program selector on each door You cannot use the manual selector...

Page 63: ...ration includes the following steps a the person approaching from the outside activates the external radar of door 1 and door 1 opens b the person enters the inner area between the two doors and engag...

Page 64: ...e de energised from the inside G 1 ON OFF key selector allowing the electromagnet to be de energised from the outside in case of emergency 31 1 ELECTRIC CONNECTIONS 17 24V 16 8 EXT RAD 9 INT RAD 11 CO...

Page 65: ...cts the closed door status ON for electromagnet equipped with open closed status sensor Connect the N O output contact of the electromagnet built in status sensor to the AUX1 input of the LCB control...

Page 66: ...counter and the event memory see paragraph 24 MAINTENANCE Warning Any potentially damaged or worn component must be replaced Make use of original spare parts only for this purpose check LABEL Parts li...

Page 67: ...on Neptis Plus has been realized to be incorporated in a machinery or to be assembled with other devices to constitute a machinery covered by Machine Directive 2006 42 EC Harmonized European regulatio...

Page 68: ...NEPTIS PLUS Made in Italy by S p A Via Ilariuzzi 17 A S Pancrazio P se 43126 PARMA ITALY Tel 39 05 21 67 52 Fax 39 05 21 67 52 22 infocom labelspa it www labelspa com...

Reviews: