27
15) SAFETY SENSORS
This section describes how to connect and setup correctly some of the safety sensors compliant with the standard EN12987 available on
the market, to ensure a safety level which corresponds to PL = c, Category 2 as provided for by the standard EN16005.
15.1) SAFETY SENSOR OA-EDGE T
This section describes how to connect and setup the safety sensors in accordance with the standard EN16005.
OA-EDGE T SENSOR WIRING
Neptis Plus AUTOMATION PWB TERMINAL BOARD
Wiring between the sensor and the terminal of the control unit PWB
1. WHITE
(+)
Power supply
TERMINAL 17 (+)
2. BROWN
(-)
Power supply
TERMINAL 16 (-)
3. GREEN
COM (Closing side)
TERMINAL 3 COM
4. YELLOW
N.C. (Closing side)
TERMINAL
2
Closing safety sensor
5. GREY
N.O. (Closing side)
do not connect
6. PINK
COM (Opening side)
TERMINAL 7 COM
7. BLUE
N.C. (Opening side)
TERMINAL
5
Opening safety sensor
8. RED
N.O. (Opening side)
do not connect
9. BLACK
(+)
Test input
TERMINAL 25 TEST(+)
10. VIOLET
(-)
Test input
TERMINAL
26 GND (-)
DIP SWITCH SETTING ON OA-EDGE T
PARAMETERS ON DIGITAL SELECTOR ET-DSEL
A7 = ON
Low level test input.
A8 = OFF
Input test delay 10msec.
B4 = OFF
Sensor installed on opening side.
B4 = ON
Sensor installed on closing side.
F11 (S05) = ON
Closing safety sensor
F12 (S06) = ON
Opening safety sensor
F13 (S07) = ON
TEST of closing safety sensor
F14 (S08) = ON
TEST of opening safety sensor
F15 (S09) = OFF
Test level LOW
15.2) FLAT SCAN SAFETY SENSOR
FLAT SCAN SENSOR WIRING
Neptis Plus AUTOMATION PWB TERMINAL BOARD
Wiring between the sensor and the terminal of the control unit PWB
1. GREEN
(+)
Power supply
TERMINAL 17 (+)
2. BROWN
(-)
Power supply
TERMINAL 16 (-)
3. YELLOW
COM (Opening side)
TERMINAL 7 COM
4. WHITE
N.C. (Opening side)
TERMINAL
5
Opening safety sensor
5. PINK
COM (Closing side)
TERMINAL 3 COM
6. GREY
N.C. (Closing side)
TERMINAL
2
Closing safety sensor
7. RED
(+)
Test input
TERMINAL 25 TEST(+)
8. BLUE
(-)
Test input
TERMINAL
26 GND (-)
DIP SWITCH SETTING ON FLAT SCAN
PARAMETERS ON DIGITAL SELECTOR ET-DSEL
DIP 1 ON
Sensor installed on opening side.
DIP 1 OFF
Sensor installed on closing side.
F11 (S05) = ON
Closing safety sensor
F12 (S06) = ON
Opening safety sensor
F13 (S07) = ON
TEST of closing safety sensor
F14 (S08) = ON
TEST of opening safety sensor
F15 (S09) = OFF
Test level LOW
The safety sensor operation test is carried out at the beginning of each door opening and closing cycle.
Should the sensor fail to properly respond to the test request by the automation control unit, the control unit buzzer will beep
and the leaf motion speed will be slow throughout the entire run.