42
P19
Push & close
If the stationary open door is pushed manually, an automatic closing cycle starts.
Increasing the value increases the degrees of leaf motion required before starting the closing. Adjustment
between 2° and 15°.
S
P20
Wind stop when the door is open
Increasing the value increases the intensity of the force contrasting the wind thrust to keep the stationary
leaf open.
S
P21
Acceleration ramp when opening
Increasing the value increases door acceleration during the opening movement.
S
P22
•
Assisted manual opening (for NB-SLT/LET spring automations only)
Increasing the value increases the feeling of lightness of the leaf during manual opening. At the
minimum value 0% the assisted function is disabled.
•
Door closing virtual spring (for NB-SMT springless automations only)
Door new closing after a manual opening.
At value = 00 the function is disabled and the door does not close again after a manual opening.
Setting the value 01, the door closes with the minimum force. Increasing the value, the thrust force
during closing increases.
S
P23
•
Spring aid when closing (only active with F38 = OFF)
for NB-SLT/LET spring automations
Increasing the value increases the force of the thrust at the start of the closing manoeuvre, for
situations in which the force of the spring is not sufficient to guarantee the start of the closing
movement.
•
Door closing virtual spring aid (for NB-SMT springless automations only)
Increasing the value, the starting force increases when the door must start its closing motion after
manual push opening, for situations in which the start of the reclosing movement is difficult.
S
P24
Distance from the final closing ledge where the door reopens if an obstacle is detected during
the closing cycle
Increasing the value increases the degrees from the final closing ledge in which the closing movement
stop is achieved without reversing the running direction in case of detection of an obstacle.
S
P25
Intensity of door braking at the end of the opening after a manual push
Increasing the value increases the leaf braking.
S
P26
Distance from the end of the run during opening, starting from which it is braked after a manual
push
Increasing the value increases the distance from the final ledge in opening where the door is braked
during the manual push.
S
P27
Leaf braking intensity when the opening safety sensor trips
Increasing the value reduces the braking distance.
S
P28
Potentiometer enabled if
the function F26 = ON
Time after which the interlock between two automatic doors gets disabled if the open door
doesn't close back
Please refer to the "Interlock system" paragraph. At the default value 0%, the function is disabled.
Time after which the interlock is disabled automatically if the door that is open does not close due to the
high flow of people. In this case, if the radar inside the second door is activated by the persons in the
space between the two doors, the second door opens allowing the outflow of people.
At 01% the interlock disabling time and the ensuing second door opening time will be 10 seconds.
At 50% the interlock disabling time will be 60 seconds, at 100% the interlock disabling time will be 120
seconds.
P29
For NB-SMT springless
automations only
Pause time before door reclosing in the virtual spring function after a manual opening
If the virtual spring function is enabled, this potentiometer adjusts the waiting time before door new
closing after the door was opened with a manual push.
Pause time adjustable from 1 to 6 seconds.
P30
Leaf delay during opening
For dual leaf door. Increasing the value increases the starting delay during opening of the Slave
automation with respect to the Master automation, necessary in case of overlapping leaves.
At the minimum value 0%, both leaves start together during opening.